5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
112
7545652/00 EN
VACUTAP
®
VR-Ex
2. Slowly lower the potential connection unit onto the pre-mounted carrier on
the change-over selector so that the studs on the carriers engage with the
openings on the potential connection unit, and the drilled holes in the car-
riers and potential connection unit align.
Figure 115: Lowering potential connection unit
3. Carefully drive in the locking pins provided from the outside until they are
seated centrally.