5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
46
7545652/00 EN
VACUTAP
®
VR-Ex
5. Remove on-load tap-changer head cover.
Figure 22: On-load tap-changer head cover
5.3.1.2.1.2 Removing tap position indicator disk
► Pull spring clip off shaft end and remove tap position indicator disk.
Figure 23: Tap position indicator disk
5.3.1.2.1.3 Removing the tap-change supervisory device
DANGER
Electric shock!
If supply voltage is applied to the tap-change supervisory device, this can
result in electric shock.
► Disconnect the tap-change supervisory device from the supply voltage
and secure it to prevent it from being switched back on again.
NOTICE
Damage to the tap-change supervisory device!
Removing the tap-change supervisory device without due care may damage
the tap-change supervisory device, thereby resulting in damage to the on-
load tap-changer.
► Remove the tap-change supervisory device with care in order not to dam-
age or rip out the connecting leads.