5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
135
7545652/00 EN
VACUTAP
®
VR-Ex
5.4.2.4 Connecting the potential connection unit
► Connect leads to the angle connectors on the potential connection unit us-
ing cable shoes and M8 screws as specified in the connection diagram
provided (cable shoes and fastening materials are not included in the
scope of delivery). Make sure that the leads are not exerting any mechani-
cal loads on the potential connection unit.
Figure 141: Angle connector of potential connection unit
1 Angle connector for customer connection
5.4.2.5 Connecting on-load tap-changer take-off lead
1. Connect the on-load tap-changer take-off lead to any through-hole on the
take-off ring using the cable shoe and screw. The cable shoe and fasten-
ing materials are not included in the scope of delivery.