MODEL: M6DXAR

Euro Terminal Ultra-Slim Signal Conditioners M6D Series

RTD ALARM

(PC programmable)
Functions & Features
• 5.9-mm wide ultra-slim design
• Low profile allows the M6D module mounted in a 120-mm
deep panel
• Provides a relay contact output at preset DC input levels
• PC programmable
• Linearization and upscale and downscale burnout
protection
• High-density mounting
• Power and status indicator LEDs

5.9 (.23)

94

(3.70)

102

(4.02)

mm (inch)

MODEL: M6DXAR–[1]–R

ORDERING INFORMATION

• Code number:  M6DXAR-[1]-R
  Specify a code from below for [1].
   (e.g. M6DXAR-4-R)
• Temperature range (e.g. 0 – 100°C)

[1] INPUT RTD

1: JPt 100 (JIS'89)
(Usable range: -200 to +500°C, -328 to +932°F)
3: Pt 100 (JIS'89)
(Usable range: -200 to +650°C, -328 to +1202°F)
4: Pt 100 (JIS'97, IEC)
(Usable range: -200 to +850°C, -328 to +1562°F)
5: Pt 50 Ω (JIS'81)
(Usable range: -200 to +649 °C, -328 to +1200°F)
7: Pt 1000
(Usable range: -200 to +850°C, -328 to +1562°F)
9: Cu 10 @25°C
(Usable range: -50 to +250°C, -58 to +482°F)
0: Specify (Please provide a resistance table.)

(Configurator software is used to change the input type and
range.  Input code 7: Pt 1000 cannot be switched to/from
other input types while its temperature range can be
changed.)

OUTPUT

Relay; SPDT or transfer contact

POWER INPUT

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

RELATED PRODUCTS

• PC configurator software (model: M6CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC.  Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.

GENERAL SPECIFICATIONS

Connection
Input and output: Euro terminal (torque 0.3 N·m)
Power input: Via the Installation Base (model: M6DBS)
or  Euro terminal (torque 0.3 N·m)
Applicable wire size: 0.2 to 2.5 mm

2

Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Burnout: Upscale standard; downscale or no burnout
optional by programming
In case of upscale standard, the alarm operates as if the
input signal has exceeded over the range.
Linearization: Standard
Power LED: Green light turns on when the power is supplied.
Status indicator LED: Orange LED; Flashing patterns
indicate different operating status of the transmitter.
Alarm monitor LED: Red LED turns on when the alarm is
tripped.
Programming: Downloaded from PC
Input type and range
Input fine adjustments
User’s RTD table (max. 300 points)
Burnout (Upscale, downscale or no burnout)
Alarm setpoint (input %)
Trip action (High or Low)
Relay coil (energized or de-energized)
Power ON delay time (0 to 999 sec.)
Alarm ON delay time (0 to 999 sec.)
Hysteresis (deadband) (input %)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for M6DXAR

Page 1: ...ELATED PRODUCTS PC configurator software model M6CFG Downloadable at M System s web site A dedicated cable is required to connect the module to the PC Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types GENERAL SPECIFICATIONS Connection Input and output Euro terminal torque 0 3 N m Power input Via the Installation Base model M6...

Page 2: ...to 55 C 4 to 131 F Operating humidity 30 to 90 RH non condensing Mounting Installation Base model M6DBS or DIN rail Weight 65 g 2 3 oz PERFORMANCE in percentage of span Setpoint accuracy trip point accuracy Pt and JPt Whichever greater 0 1 of input range or 0 15 C Cu10 1 C Temp coefficient 0 01 C 0 006 F of max span Response time 1 sec 0 100 at 90 setpoint Burnout response time 1 sec Line voltage ...

Page 3: ... RAIL HOOK 102 4 02 0 5 02 8 M3 EURO TERMINAL DIN RAIL 35mm wide 5 6 7 8 1 2 3 4 When mounting no extra space is needed between units WIRE INSERTION ANGLE approx 7 SCREWDRIVER INSERTION ANGLE approx 40 Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Page 4: ...oad Coil Diode Varistor or CR Circuit Low Drift Amplifier STATUS LED ALARM MONITOR LED POWER Digital Computation Ry JACK CONFIGURATOR RTD 2 wire 3 wire OUTPUT CONNECTOR POWER POWER LED Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Page 5: ...hat appropriate clearance and creepage distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 0 5W GENERAL PRECAUTIONS Before you remove the unit or mount i...

Page 6: ...DIN rail adaptor using a minus screw driver B Pull out the lower part of the unit C Remove the upper part from the DIN rail DIN Rail A B DIN Rail Adaptor A B C COMPONENT IDENTIFICATION Body Front Cover DIN Rail Adaptor Spec Marking Status Indicator LED Configurator Jack Power LED Alarm Monitor LED FRONT VIEW with the cover open Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 ...

Page 7: ...L DIN RAIL 35mm wide 5 6 7 8 1 2 3 4 When mounting no extra space is needed between units WIRE INSERTION ANGLE approx 7 SCREWDRIVER INSERTION ANGLE approx 40 7 8 2 4 3 NC NO COM A B A B B 6 1 5 RTD 2 wire 3 wire CONFIGURATOR JACK OUTPUT POWER 8 mm 8 mm 3 7 mm dia max 3 7 mm dia max Wire exposure Recommended ferruled wire How to Connect Wires Insert a wire Confirm that the wire tip hits the bottom ...

Page 8: ...ined below CALIBRATION Warm up the unit for at least 10 minutes H Setpoint Increase the input signal from a value lower than the set point and check that the relay trips at the H setpoint within the setpoint accuracy described in the data sheet L Setpoint Decrease the input signal from a value higher than the set point and check that the relay trips at the L setpoint within the setpoint accuracy d...

Reviews: