M6DXAR

CHECKING

1)  Terminal wiring: Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage: Check voltage across the terminal 

7– 8 with a multimeter.

3)  Input: Check that the input signal is within 0 – 100% of 

the full-scale.

  If the RTD or its extension wires are broken, the output 

goes  over  100%  (below  0%  with  downscale  protection) 
due to the burnout function.  Confirm the status indica-
tor LED pattern and check leadwires in such a case.

4)  Alarm operations: Check the alarm operations referring 

to the figure below.

5)  Output  load:  Check  that  the  output  load  is  250V  AC/

500VA or 125V DC/60W.  For maximum relay life with 
inductive load, external protection is recommended.

LED FUNCTIONS

 STATUS INDICATOR LED

The  M6DXAR  is  provided  with  a  status  indicator  LED 
which  flashes  in  different  patterns  indicating  various  op-
erating status.
The following figure indicates typical patterns.

 ALARM MONITOR LED

The  M6DXAR  is  provided  with  an  alarm  monitor  LED 
which flashes in different patterns indicating various alarm 
status.
The following figure indicates typical patterns.

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.

• H Setpoint

Increase the input signal from a value lower than the set-
point and check that the relay trips at the H setpoint within 
the setpoint accuracy described in the data sheet.

• L Setpoint

Decrease the input signal from a value higher than the set-
point and check that the relay trips at the L setpoint within 
the setpoint accuracy described in the data sheet.
When the setpoints are shifted, recalibrate the unit using 
the PC Configurator Software (model: M6CFG).

LIGHTNING SURGE PROTECTION

In order to protect the unit from lightning surges entering 
through power supply cables, use of appropriate lightning 
surge protectors are recommended.  Please contact M-Sys-
tem.

0

50

100

Input
(%)

Setpoint

Output

(3–4)ON

(3–2)ON

• Setting Example
     Hi alarm (coil energized at alarm) or
     Lo alarm (coil de-energized at alarm)

Alarm Trip Operation  

Terminal No. in parentheses

Trip operation in power failure

: Terminals 3 – 4 turn ON.

TRANSMITTER STATUS

LED ON-OFF PATTERNS

Normal operating mode

Abnormal operating mode

Burnout mode

ON

OFF

80 milliseconds

Power ON delay

ALARM STATUS

ON

OFF

LED ON-OFF PATTERNS

Alarm ON delay

Alarm OFF

Alarm ON

160 millisec.

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for M6DXAR

Page 1: ...ELATED PRODUCTS PC configurator software model M6CFG Downloadable at M System s web site A dedicated cable is required to connect the module to the PC Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types GENERAL SPECIFICATIONS Connection Input and output Euro terminal torque 0 3 N m Power input Via the Installation Base model M6...

Page 2: ...to 55 C 4 to 131 F Operating humidity 30 to 90 RH non condensing Mounting Installation Base model M6DBS or DIN rail Weight 65 g 2 3 oz PERFORMANCE in percentage of span Setpoint accuracy trip point accuracy Pt and JPt Whichever greater 0 1 of input range or 0 15 C Cu10 1 C Temp coefficient 0 01 C 0 006 F of max span Response time 1 sec 0 100 at 90 setpoint Burnout response time 1 sec Line voltage ...

Page 3: ... RAIL HOOK 102 4 02 0 5 02 8 M3 EURO TERMINAL DIN RAIL 35mm wide 5 6 7 8 1 2 3 4 When mounting no extra space is needed between units WIRE INSERTION ANGLE approx 7 SCREWDRIVER INSERTION ANGLE approx 40 Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Page 4: ...oad Coil Diode Varistor or CR Circuit Low Drift Amplifier STATUS LED ALARM MONITOR LED POWER Digital Computation Ry JACK CONFIGURATOR RTD 2 wire 3 wire OUTPUT CONNECTOR POWER POWER LED Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Page 5: ...hat appropriate clearance and creepage distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 0 5W GENERAL PRECAUTIONS Before you remove the unit or mount i...

Page 6: ...DIN rail adaptor using a minus screw driver B Pull out the lower part of the unit C Remove the upper part from the DIN rail DIN Rail A B DIN Rail Adaptor A B C COMPONENT IDENTIFICATION Body Front Cover DIN Rail Adaptor Spec Marking Status Indicator LED Configurator Jack Power LED Alarm Monitor LED FRONT VIEW with the cover open Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 ...

Page 7: ...L DIN RAIL 35mm wide 5 6 7 8 1 2 3 4 When mounting no extra space is needed between units WIRE INSERTION ANGLE approx 7 SCREWDRIVER INSERTION ANGLE approx 40 7 8 2 4 3 NC NO COM A B A B B 6 1 5 RTD 2 wire 3 wire CONFIGURATOR JACK OUTPUT POWER 8 mm 8 mm 3 7 mm dia max 3 7 mm dia max Wire exposure Recommended ferruled wire How to Connect Wires Insert a wire Confirm that the wire tip hits the bottom ...

Page 8: ...ined below CALIBRATION Warm up the unit for at least 10 minutes H Setpoint Increase the input signal from a value lower than the set point and check that the relay trips at the H setpoint within the setpoint accuracy described in the data sheet L Setpoint Decrease the input signal from a value higher than the set point and check that the relay trips at the L setpoint within the setpoint accuracy d...

Reviews: