background image

M6DXAR

P.  / 4

EM-7855

INSTALLATION

Set the unit so that its DIN rail adapter is at the bottom.

 

 MOUNTING THE UNIT ON A DIN RAIL

A) Hang the upper hook at the rear side of unit on the DIN 

rail.

B) Push  in  the  lower  in  keeping  pressing  the  unit  to  the 

DIN rail.

 REMOVING THE UNIT

A) Pull  down  the  DIN  rail  adaptor  using  a  minus  screw-

driver.

B) Pull out the lower part of the unit.
C) Remove the upper part from the DIN rail.

DIN Rail

A

B

DIN Rail Adaptor

A

B

C

COMPONENT IDENTIFICATION

Body

Front Cover

DIN Rail Adaptor

Spec. Marking

Status Indicator LED

Configurator Jack

Power LED

Alarm Monitor LED

 FRONT VIEW (with the cover open)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for M6DXAR

Page 1: ...ELATED PRODUCTS PC configurator software model M6CFG Downloadable at M System s web site A dedicated cable is required to connect the module to the PC Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types GENERAL SPECIFICATIONS Connection Input and output Euro terminal torque 0 3 N m Power input Via the Installation Base model M6...

Page 2: ...to 55 C 4 to 131 F Operating humidity 30 to 90 RH non condensing Mounting Installation Base model M6DBS or DIN rail Weight 65 g 2 3 oz PERFORMANCE in percentage of span Setpoint accuracy trip point accuracy Pt and JPt Whichever greater 0 1 of input range or 0 15 C Cu10 1 C Temp coefficient 0 01 C 0 006 F of max span Response time 1 sec 0 100 at 90 setpoint Burnout response time 1 sec Line voltage ...

Page 3: ... RAIL HOOK 102 4 02 0 5 02 8 M3 EURO TERMINAL DIN RAIL 35mm wide 5 6 7 8 1 2 3 4 When mounting no extra space is needed between units WIRE INSERTION ANGLE approx 7 SCREWDRIVER INSERTION ANGLE approx 40 Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Page 4: ...oad Coil Diode Varistor or CR Circuit Low Drift Amplifier STATUS LED ALARM MONITOR LED POWER Digital Computation Ry JACK CONFIGURATOR RTD 2 wire 3 wire OUTPUT CONNECTOR POWER POWER LED Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Page 5: ...hat appropriate clearance and creepage distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 0 5W GENERAL PRECAUTIONS Before you remove the unit or mount i...

Page 6: ...DIN rail adaptor using a minus screw driver B Pull out the lower part of the unit C Remove the upper part from the DIN rail DIN Rail A B DIN Rail Adaptor A B C COMPONENT IDENTIFICATION Body Front Cover DIN Rail Adaptor Spec Marking Status Indicator LED Configurator Jack Power LED Alarm Monitor LED FRONT VIEW with the cover open Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 ...

Page 7: ...L DIN RAIL 35mm wide 5 6 7 8 1 2 3 4 When mounting no extra space is needed between units WIRE INSERTION ANGLE approx 7 SCREWDRIVER INSERTION ANGLE approx 40 7 8 2 4 3 NC NO COM A B A B B 6 1 5 RTD 2 wire 3 wire CONFIGURATOR JACK OUTPUT POWER 8 mm 8 mm 3 7 mm dia max 3 7 mm dia max Wire exposure Recommended ferruled wire How to Connect Wires Insert a wire Confirm that the wire tip hits the bottom ...

Page 8: ...ined below CALIBRATION Warm up the unit for at least 10 minutes H Setpoint Increase the input signal from a value lower than the set point and check that the relay trips at the H setpoint within the setpoint accuracy described in the data sheet L Setpoint Decrease the input signal from a value higher than the set point and check that the relay trips at the L setpoint within the setpoint accuracy d...

Reviews: