The status word, P 2682[0] - CON_PRC_StatWord, indicates the process
controller’s current state.
Bit
Name
Description
0
On
Process controller active
1
ResetIReady
Integral term reset complete
Table 7.3
3
: Status word
P 2682[0]
Fig. 7.42: Process controller state machine
MOOG
ID
No.:
CB40859-001
Date:
02/2018
MSD Servo Drive - Device Help
155
7 Control
In addition to the process controller status word, bit 8 of the device status word,
P 702[0] - MON_State, will be set when the setpoint is reached. P 2679[0] - CON_
PRC_RefReached can be used to configure the “Reference value attained” window
for this purpose. Bit 8 will be set to TRUE if the process controller’s deviation is less
than 50 % of the configured “Reference value attained” window.
7.10.2.2 Reference values
The process control circuit setpoint can be selected via pre-defined setpoint sources.
P 2683[0] - CON_PRC_REFSEL can be used to select these setpoint sources.
Setting
Name
Description
0
USER
User input via
CON_PRC_REFVAL_
User - P2684
1
RPDC
Automatic input of transmitted RPDC
current value
2
ANA0
Analog input ISA00 (CON_ANA_Isaf[0])
3
ANA1
Analog input ISA01 (CON_ANA_Isaf[1])
4
Reserved
Special hardware required
5
Reserved
Special hardware required
6
ANA_ALL
Any analog input (function selector for
analog inputs set to a value of -13)
7
P2981
Mappable parameter P-2981
8
P2982
Mappable parameter P-2982
9
P2983
Mappable parameter P-2983
10
P2984
Mappable parameter P-2984
Table 7.3
4
: Selector for reference value source