19. MULTI-CHANNEL FUNCTION
19.3 GOT Side Settings
19 - 9
19
MUL
T
I-CH
ANNEL FUNC
TION
Calculating consumed current
For using multiple extension units, a bar code reader, or a RFID controller, the total current for the extension units,
bar code reader, or RFID controller must be within the current that the GOT can supply.
For the current that the GOT can supply and the current for the extension units, bar code reader, or RFID controller,
refer to the following tables. Make sure that the total of consumed current is within the capacity of the GOT.
(1) Current supply capacity of the GOT
(2) Current consumed by an extension unit/barcode reader/RFID controller
*1
Value used for calculating the current consumption of the multi-channel function.
For the specifications of the unit, refer to the manual included with the unit.
*2
When the GOT supplies power to a barcode reader or an RFID controller from the standard interface, add their consumed
current. (Maximum value is less than 0.3 A)
GOT type
Capacity
(A)
GT2712-S
GT2710-S
GT2710-V
GT2708-S
GT2708-V
Module type
Consumed
current
(A)
Module type
Consumed
current
(A)
GT15-QBUS,
GT15-QBUS2,
GT15-75QBUSL,
GT15-75QBUS2L
0.275
*1
GT27-V4-Z
0.12
*1
GT15-ABUS,
GT15-ABUS2,
GT15-75ABUSL,
GT15-75ABUS2L
0.12
GT27-R2-Z
0
*1
GT15-RS2-9P
0.29
GT27-V4R1-Z
0.12
*1
GT15-RS4-9S
0.33
GT27-ROUT-Z
0.11
*1
GT15-RS4-TE
0.3
GT27-MMR-Z
0.27
*1
GT15-J71GP23-SX
1.07
GT15-SOUT
0.08
GT15-J71GF13-T2
0.96
GT15-DIO
0.1
GT15-J71LP23-25
0.56
GT15-DIOR
0.1
GT15-J71BR13
0.77
Bar code reader
*2
GT15-J61BT13
0.56
Summary of Contents for GOT2000 Series
Page 2: ......
Page 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 64: ......
Page 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Page 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Page 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Page 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Page 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Page 416: ......
Page 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Page 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Page 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Page 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Page 542: ......
Page 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Page 568: ......
Page 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Page 600: ......
Page 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Page 670: ...REVISIONS 2 ...
Page 673: ......