14. INVERTER CONNECTION
14.5 FREQROL Series Inverter Side Settings
14 - 39
INVERTE
R CONNECTION
14
(4) Communication settings of inverter (Manual setting)
Set the following parameters using the PU (operation panel or parameter unit). Before setting the parameters,
set Pr.160 (User group read selection) to 0 so that simple mode + extended parameters are displayed. (The
default value of FREQROL-F800 is 9999.)
Do not change these parameters, even though they can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Setting items are parameter names described in the manual of FREQROL-A800, F800 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change the parameters on the inverter to correspond with the GOT settings.
*3
Since the value has been set as a default, no setting is required when connecting to the PU connector on the inverter side.
*4
To use the FREQROL 800 driver, set 0.
*5
Inverter default values (No need to change).
*6
The inverter side setting defaults to 0 (invalid).
To use the PLC function, set 1 or 2.
Setting item
*1
Parameter No.
Set value
Contents of setting
PU connector
RS-485
PU communication station number/
RS-485 communication station number
Pr.117
Pr.331
0 to 31
PU communication speed/
RS-485 communication speed
*2
Pr.118
Pr.332
192
*3
19200bps
PU communication stop bit length/data length/
RS-485 communication stop bit length/data length
*2
Pr.119
Pr.333
10
*4
Data length: 7bit
Stop bit length: 1bit
PU communication parity check/
RS-485 communication parity check
*2
Pr.120
Pr.334
1
Odd
Number of PU communication retries/
RS-485 communication retry count
Pr.121
Pr.335
9999
The inverter will not come to an
alarm stop.
PU communication check time interval/
RS-485 communication check time interval
Pr.122
Pr.336
9999
*3
Communication check
suspension
PU communication waiting time setting/
RS-485 communication waiting time setting
Pr.123
Pr.337
0
0ms
PU communication CR/LF selection/
RS-485 communication CR/LF selection
Pr.124
Pr.341
1
*5
With CR, without LF
Protocol selection
-
Pr.549
0
*5
Mitsubishi inverter protocol
Operation mode selection
Pr.79
PU
connector
1
PU operation mode
RS-485
0
*5
External operation mode at
power on
Communication startup mode selection
Pr.340
PU
connector
0
*5
Refer to Pr.79 settings.
RS-485
1
Network operation mode.
Communication EEPROM write selection
Pr.342
0
*5
Written to RAM and EEPROM
PLC function operation selection
*6
Pr.414
1, 2
Enabled with 1 and 2.
Summary of Contents for GOT2000 Series
Page 2: ......
Page 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 64: ......
Page 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Page 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Page 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Page 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Page 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Page 416: ......
Page 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Page 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Page 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Page 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Page 542: ......
Page 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Page 568: ......
Page 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Page 600: ......
Page 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Page 670: ...REVISIONS 2 ...
Page 673: ......