13. CC-Link CONNECTION (Via G4)
13.5 PLC Side Settings
13 - 15
C
C
-Link CONNEC
T
ION (V
ia
G4)
13
13.5.3
Switch setting of CC-Link
module (Q series)
Set the station number setting switch, transmission speed /
mode setting switch.
(1) Station number setting switch
: Necessary
: As necessary
: Not necessary
(2) Transmission rate/mode setting switch
: Necessary
: As necessary
: Not necessary
POINT
POINT
POINT
When the switch setting has been changed
Turn the PLC CPU OFF then ON again, or reset the
PLC CPU.
13.5.4
[Network parameter] of GX
Developer
(1) Network parameter
: Necessary
: As necessary
: Not necessary
Station number
setting switch
Description
Set value
Setting
necessity
at GOT
connection
Station number setting
(master station)
0 (fixed)
Transmission
rate/
mode setting
switch
Description
Set value
Setting
necessity
at GOT
connection
Transmission rate/mode
setting
0: 156kbps
1: 625kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps
(1)
(2)
QJ61BT11, QJ61BT11N
0
5
0
5
0
8
1
2
7
6
5
4
3
STATION
NO.
X10
X1
MODE
QJ61BT11N
RUN
ERR.
SD
MST
L RUN
L ERR.
RD
S MST
NC
DA
DB
NC
SLD
DG
(FG)
C
4
0
5
0
5
STATION
NO.
X10
X1
0
8
MODE
C
4
Item
Set value
Setting necessity
at GOT
connection
No. of boards in module
1
Start I/O No.
0000
H
Operation setting
(Use default value)
Type
Master station (fixed)
Mode
Remote net (Ver.1 mode)
All connect count
1
Remote input (RX)
X400
Remote output (RY)
Y400
Remote register (RWr)
D300
Remote register (RWw)
D200
Special relay (SB)
SB0
Special register (SW)
SW0
Retry count
(Use default value)
Automatic reconnection
station count
Stand by master station No.
PLC down select
Scan mode setting
Delay information setting
Station information setting
Refer to (2)
Remote device station
initial setting
(Use default value)
Interrupt setting
Summary of Contents for GOT2000 Series
Page 2: ......
Page 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 64: ......
Page 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Page 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Page 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Page 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Page 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Page 416: ......
Page 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Page 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Page 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Page 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Page 542: ......
Page 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Page 568: ......
Page 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Page 600: ......
Page 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Page 670: ...REVISIONS 2 ...
Page 673: ......