12. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
12.4 PLC Side Setting
12 - 31
CC-Link CON
N
ECTION
(IN
T
ELLIGENT DEVIC
E ST
A
T
ION)
12
[Controller Setting] of GT Designer3
POINT
POINT
POINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
12.3.1 Setting communication interface
(Communication settings)
12.4.7
Connecting to CC-Link module
(A Series)
This section describes the settings of the GOT and CC-
Link module (A Series) in the following case of system
configuration.
POINT
POINT
POINT
CC-Link module (A Series)
For details of the CC-Link module (A Series), refer to
the following manual.
Control & Communication Link System Master/
Local Module Type AJ61BT11/A1SJ61BT11
User's Manual
System configuration
*1
The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0"
Item
Set value
Station No.
1: Station No.1
Transmission Rate
0: Online 156kbps
Mode
Ver.1: Remote net (Ver.1 mode)
Expanded Cyclic
Single (Use default value)
Number of stations occupied
1 Station
Input for Error Station
0: Clear
Retry
3times (Use default value)
Timeout Time
3sec (Use default value)
Delay Time
0ms (Use default value)
*1
<CC-Link module>
(Use the default value for settings other than the following.)
<GOT>
(Use the default value for settings other
than the following.)
Station type
: Master station
All connect count
: 1
Mode setting
: Remote net mode
Station No.
: Station No.0
Module mode
: Intelligent mode
Transmission speed : 156kbps
Station type
: Intelligent device
station
Station No.
: Station No.1
Number of station occupied : Exclusive station 1
Transmission
speed
: 156kbps
■
[Controller Setting] of GT Designer3
■
Settings of CC-Link module (A Series)
■
Summary of Contents for GOT2000 Series
Page 2: ......
Page 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 64: ......
Page 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Page 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Page 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Page 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Page 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Page 416: ......
Page 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Page 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Page 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Page 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Page 542: ......
Page 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Page 568: ......
Page 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Page 600: ......
Page 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Page 670: ...REVISIONS 2 ...
Page 673: ......