11. CC-Link IE FIELD NETWORK CONNECTION
11.4 PLC Side Setting
11 - 11
C
C
-Link IE FIELD NETWORK CONNECTION
11
11.4 PLC Side Setting
This section describes the settings of the GOT and CC-
Link IE controller network module in the following case of
system configuration.
POINT
POINT
POINT
CC-Link IE Field Network Module
For details of the CC-Link IE Field Network module,
refer to the following manual.
CC-Link IE Field Network Master/Local Module
User's Manual
System configuration
(Network Type: CC IE Field)
*1
The CC-Link IE Field Network module is mounted on slot 0
of the base unit.
The start I/O No. of the CC-Link IE Field Network module is
set at [0].
POINT
POINT
POINT
When connecting to Q170MCPU or Q170MSCPU(-S1)
When connected to Q170MCPU or Q170MSCPU(-
S1), the start I/O No. of the CC-Link IE Field Network
communication unit is set to "70".
Parameter settings (Connection to MELSEC-
Q, QS series) of System configuration
(Network Type: CC IE Field)
(1) Network parameter] of GX Works2
Use GX Works2 of Version 1.31H or later.
(a) Network parameter
: Necessary
: As necessary
: Not necessary
*1
When using Q170MCPU or Q170MSCPU(-S1), set it
according to the system configuration.
*2
Specify the same network No. as that of the GOT.
*3
Set the same mode setting as that of the GOT.
<CC-Link IE Field Network module> *
1
(Use the default value for settings other than the following.)
Station No.
: 0 (fixed)
Mode
: Online (normal)
Network type
: CC IE Field (Master station)
Network No.
: 1
Total stations
: 1
Network Configuration Settings :
CC-Link IE Field Network
<GOT>
(Use the default value for settings other
than the following.)
RX/RY00
H
to FFH
RW
W/
RW
r
00
H
to FFH
Network type
: CC IE Field
Network No.
: 1
Station No.
: 1
Mode Setting : Online
Network Configuration Settings :
Monitor Speed : High
RX/RY00 to FFH
RW
W/
RW
r
00 to FFH
■
GT Designer3 [Communication setting] of System
configuration1 (Network Type: CC IE Field)
■
[Network parameter] of GX Works2
Item
Set value
Setting
necessity at
GOT
connection
Network type
CC IE Field
(Master station) (fixed)
Starting I/O No.
*1
0000
H
Network No.
*2
1
Total stations
1
Station No.
0 (fixed)
Mode
*3
Online
(Normal mode)
Network Configuration
Settings
Refer to (b)
Refresh parameters
(Use default value)
Interrupt settings
Interlink transmission
parameters
Routing parameters
Refer to (c)
Summary of Contents for GOT2000 Series
Page 2: ......
Page 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Page 64: ......
Page 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Page 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Page 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Page 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Page 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Page 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Page 416: ......
Page 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Page 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Page 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Page 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Page 542: ......
Page 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Page 568: ......
Page 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Page 600: ......
Page 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Page 670: ...REVISIONS 2 ...
Page 673: ......