Causes and corrective actions
5
P
R
OTECTIVE
FUNC
TI
ONS
Operation Panel
Indication
E.PE2
FR-PU04
Fault 14
FR-PU07
PR storage alarm
Name
Parameter storage device alarm (main circuit board)
Description
A fault occurred in parameters stored (EEPROM failure)
Check point
——————
Corrective action
Please contact your sales representative.
Operation Panel
Indication
E.PUE
FR-PU04
FR-PU07
PU Leave Out
Name
PU disconnection
Description
This function stops the inverter output if communication between the inverter and PU is suspended, e.g. the
operation panel and parameter unit is disconnected, when "2", "3", "16" or "17" was set in
Pr. 75 Reset selection/
disconnected PU detection/PU stop selection
. This function stops the inverter output when communication errors
occurred consecutively for more than permissible number of retries when a value other than "9999" is set in
Pr. 121
Number of PU communication retries
during the RS-485 communication with the PU connector. This function also stops
the inverter output if communication is broken for the period of time set in
Pr. 122 PU communication check time interval
.
Check point
· Check that the FR-DU07 or parameter unit (FR-PU04/FR-PU07) is fitted tightly.
· Check the
Pr. 75
setting.
Corrective action
Fit the FR-DU07 or parameter unit (FR-PU04/FR-PU07) securely.
Operation Panel
Indication
E.RET
FR-PU04
FR-PU07
Retry No Over
Name
Retry count excess
Description
If operation cannot be resumed properly within the number of retries set, this function stops the inverter
output.
Check point
Find the cause of alarm occurrence.
Corrective action
Eliminate the cause of the error preceding this error indication.
Operation Panel
Indication
E. 6
FR-PU04
FR-PU07
Fault 6
E. 7
Fault 7
E.CPU
CPU Fault
Name
CPU error
Description
Stops the inverter output if the communication error of the built-in CPU occurs.
Check point
Check for devices producing excess electrical noises around the inverter.
Corrective action
· Take measures against noises if there are devices producing excess electrical noises around the
inverter.
· Please contact your sales representative.
Operation Panel
Indication
E.CTE
FR-PU04
⎯⎯
FR-PU07
E.CTE
Name
Operation panel power supply short circuit, RS-485 terminal power supply short circuit
Description
When the operation panel power supply (PU connector) is shorted, this function shuts off the power
output. At this time, the operation panel (parameter unit) cannot be used and RS-485 communication
from the PU connector cannot be made. When the power supply for the RS-485 terminals are shorted,
this function shuts off the power output.
At this time, communication from the RS-485 terminals cannot be made.
To reset, enter the RES signal or switch power off, then on again.
Check point
1. Check for a short circuit in the PU connector cable.
2. Check that the RS-485 terminals are connected correctly.
Corrective action
1. Check the PU and cable.
2. Check the connection of the RS-485 terminals
Operation Panel
Indication
E.MB1 to 7
FR-PU04
⎯⎯
FR-PU07
E.MB1 Fault to E.MB7 Fault
Name
Brake sequence error
Description
The inverter output is stopped when a sequence error occurs during use of the brake sequence
function (
Pr. 278
to
Pr. 285
).
(Refer to page 208)
Check point
Find the cause of alarm occurrence.
Corrective action
Check the set parameters and perform wiring properly.