![Mitsubishi FR-A740-00023-EC Instruction Manual Download Page 292](http://html1.mh-extra.com/html/mitsubishi/fr-a740-00023-ec/fr-a740-00023-ec_instruction-manual_1809251292.webp)
282
Frequency/torque setting by analog
input (terminal 1, 2, 4)
4.21.5 Bias and gain of frequency setting voltage (current)
(Pr. 125, Pr. 126, Pr. 241, C2(Pr. 902) to C7(Pr. 905), C12(Pr. 917) to C15(Pr. 918))
Frequency setting bias/gain parameter
Speed limit bias/gain parameter
You can set the magnitude (slope) of the output frequency as desired in relation to the frequency setting signal (0
to 5V, 0 to 10V or 0 to 20mADC).
Set
Pr. 73,
Pr. 267
and voltage/current input switch to switch between 0 to 5VDC, 0 to 10VDC and 4 to 20mADC.
(Refer to page 275)
Parameter
Number
Name
Initial Value
Setting
Range
Description
125
Terminal 2 frequency setting gain
frequency
50Hz
0 to 400Hz
Set the frequency of terminal 2 input gain
(maximum).
126
Terminal 4 frequency setting gain
frequency
50Hz
0 to 400Hz
Set the frequency of terminal 4 input gain
(maximum).
241
*2
Analog input display unit
switchover
0
0
Displayed in %
Select the unit of
analog input display.
1
Displayed in V/mA
C2(902)
*1
Terminal 2 frequency setting bias
frequency
0Hz
0 to 400Hz
Set the frequency on the bias side of
terminal 2 input.
C3(902)
*1
Terminal 2 frequency setting bias
0%
0 to 300%
Set the converted % of the bias side
voltage (current) of terminal 2 input.
C4(903)
*1
Terminal 2 frequency setting gain
100%
0 to 300%
Set the converted % of the gain side
voltage (current) of terminal 2 input.
C5(904)
*1
Terminal 4 frequency setting bias
frequency
0Hz
0 to 400Hz
Set the frequency on the bias side of
terminal 4 input.
C6(904)
*1
Terminal 4 frequency setting bias
20%
0 to 300%
Set the converted % of the bias side
current (voltage) of terminal 4 input.
C7(905)
*1
Terminal 4 frequency setting gain
100%
0 to 300%
Set the converted % of the gain side
current (voltage) of terminal 4 input.
Parameter
Number
Name
Initial Value
Setting
Range
Description
C12(917)
*1
Terminal 1 bias frequency (speed)
0Hz
0 to 400Hz
Set the frequency (speed) on the bias side
of terminal 1 input.
C13(917)
*1
Terminal 1 bias (speed)
0%
0 to 300%
Set the converted % of the bias side
voltage of terminal 1 input.
C14(918)
*1
Terminal 1 gain frequency (speed)
50Hz
0 to 400Hz
Set the frequency (speed) of terminal 1
input gain (maximum).
C15(918)
*1
Terminal 1 gain (speed)
100%
0 to 300%
Set the converted % of the gain side
voltage of terminal 1 input.
*1
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
*2
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection
.