257
Operation selection at power failure
and instantaneous power failure
4
P
ARAME
T
E
R
S
(4) Restart coasting time
(Pr. 57)
⋅
Coasting time is the time from when the motor speed is detected until automatic restart control is started.
⋅
Set
Pr. 57
to "0" to perform automatic restart operation. The coasting time is automatically set to the value below.
Generally this setting will pose no problems.
00052 or less . . . . 0.5s, 00083 to 00250 . . . 1s, 00310 to 01800 . . . . . 3.0s, 02160 or more . . . 5.0s
⋅
Operation may not be performed well depending on the magnitude of the moment (J) of inertia of the load or
running frequency. Adjust the coasting time between 0.1s and 5s according to the load specifications.
(5) Restart cushion time
(Pr. 58)
⋅
Cushion time is the length of time taken to raise the voltage appropriate to the detected motor speed (output
frequency prior to instantaneous power failure when
Pr. 162
= "1" or "11").
⋅
Normally the initial value need not be changed for operation, but adjust it according to the magnitude of the
moment (J) of inertia of the load or torque.
⋅
Pr. 58
is invalid during encoder feedback control (
Pr. 162
= "2, 12"), real sensorless vector control or vector control.
(6) Automatic restart operation adjustment
(Pr. 163 to
Pr. 165, Pr. 611)
⋅
Using
Pr. 163
and
Pr. 164
, you can adjust the voltage rise time at a
restart as shown on the left.
⋅
Using
Pr. 165
, you can set the stall prevention operation level at a
restart.
⋅
Using
Pr. 611
, you can set the acceleration time until the set
frequency is reached after automatic restart operation is performed
besides the normal acceleration time.
CAUTION
⋅
Changing the terminal assignment using
Pr. 178 to Pr. 189 (input terminal function selection)
may affect the other functions. Please
make setting after confirming the function of each terminal.
⋅
When automatic restart operation is selected, undervotage protection (E.UVT) and instantaneous power failure protection
(E.IPF) among the alarm output signals will not be provided at occurrence of an instantaneous power failure.
⋅
The SU and FU signals are not output during a restart. They are output after the restart cushion time has elapsed.
⋅
Automatic restart operation will also be performed after a reset made by an inverter reset is canceled or when a retry is made
by the retry function.
⋅
Automatic restart after instantaneous power failure function is invalid when load torque high speed frequency control (
Pr. 270
=
"2, 3") is set.
CAUTION
Provide mechanical interlocks for MC1 and MC2. The inverter will be damaged if the power supply is input to the
inverter output section.
When automatic restart after instantaneous power failure has been selected, the motor and machine will start
suddenly (after the reset time has elapsed) after occurrence of an instantaneous power failure. Stay away from
the motor and machine. When you have selected automatic restart after instantaneous power failure function,
apply in easily visible places the CAUTION stickers supplied to the installation guideline.
♦
Parameters referred to
♦
Pr. 7 Acceleration time, Pr. 21 Acceleration/deceleration time increments
Refer to page 167
Pr. 13 Starting frequency
Refer to page 169
Pr. 65, Pr. 67 to Pr. 69 Retry function
Refer to page 261
Pr. 78 Reverse rotation prevention selection
Refer to page 299
Pr. 178 to Pr. 189 (input terminal function selection)
Refer to page 222
Voltage
100%
Pr.164
(Pr.163) Pr.58
Time
REMARKS
⋅
If the setting of
Pr. 21 Acceleration/deceleration time increments
is
changed, the setting increments of
Pr. 611
does not change.