118
Torque control by real sensorless vector
control, vector control
(3) Torque command using parameters (
Pr. 804
= "1")
(4) Torque command by CC-Link communication (
Pr. 804
= "3, 5, 6")
⋅
Writing a value to
Pr. 805
or
Pr. 806
using the FR-A7NC (communication option) sets the torque command value.
⋅
When "3 or 5" is set in
Pr.804
, torque command can be set in remote resister RWw1 or RWwC using the FR-A7NC
(communication option).
⋅
By setting "5, 6" in
Pr.804
, the range of torque command setting from FR-A7NC (communication option) is set from
-327.68% to 327.67% (0.01% increments).
(5) Torque command by 16 bit digital input (
Pr. 804
= 4)
⋅
Give a torque command by 16 bit or 12 bit digital input using the FR-A7AX (plug-in option).
(6) Change the torque characteristics in the constant power (
Pr. 803
)
⋅
Torque command value can be set by setting
Pr. 805
Torque command value (RAM)
or
Pr. 806 Torque command
value (RAM,EEPROM)
.
⋅
For
Pr. 805
or
Pr. 806
, the torque command is set by an
offset from 1000% on the assumption that 1000% is 0%.
The relationship between the
Pr. 805
or
Pr. 806
setting
and actual torque command value at this time is shown
on the left.
⋅
When changing the torque command frequently, write to
Pr. 805
. Performing frequent parameter write
to
Pr. 806
will
shorten the life of the EEPROM.
REMARKS
⋅
When torque command is set in
Pr. 805
(RAM), powering off the inverter will erase the changed parameter values. Therefore,
the parameter value available when power is switched on again is the value set in
Pr. 806
(EEPROM).
CAUTION
⋅
When giving a torque command by parameter setting, set the speed limit value to an appropriate value to prevent overspeed.
(Refer to page 119.)
Pr. 804
Setting
Torque Command Source
Setting Range
Increments
1
Torque command by parameter setting
(Pr. 805 or Pr. 806)
600 to 1400 (-400% to 400%)
1%
3
Torque command by parameter setting
(Pr. 805 or Pr. 806)
600 to 1400 (-400% to 400%)
1%
Torque command from remote resister (RWw1 or RWwC)
with using CC-Link communication (FR-A7NC)
5
Torque command by parameter setting
(Pr. 805 or Pr. 806)
without using CC-Link communication (FR-A7NC)
600 to 1400 (-400% to 400%)
1%
Torque command by parameter setting
(Pr. 805 or Pr. 806)
with using CC-Link communication (FR-A7NC)
-32768 to 32767 (two's complement)
(-327.68% to 327.67%)
0.01%
Torque command from remote resister (RWw1 or RWwC)
with using CC-Link communication (FR-A7NC)
-32768 to 32767 (two's complement)
(-327.68% to 327.67%)
0.01%
6
Torque command by parameter setting
(Pr. 805 or Pr. 806)
without using CC-Link communication (FR-A7NC)
600 to 1400 (-400% to 400%)
1%
Torque command by parameter setting
(Pr. 805 or Pr. 806)
with using CC-Link communication (FR-A7NC)
-32768 to 32767 (two's complement)
(-327.68% to 327.67%)
0.01%
REMARKS
For details of the setting with the FR-A7NC, refer to the FR-A7NC instruction manual.
REMARKS
For details of the setting with the FR-A7AX, refer to the FR-A7AX instruction manual.
⋅
Due to the motor characteristics, torque is reduced at or
above the base frequency. Set "1" in
Pr. 803 Constant
power range torque characteristic selection
when you want
to keep the torque to be constant even at or above the
base frequency.
♦
Parameters referred to
♦
Pr. 868 Terminal 1 function assignment
Refer to page 94.
Calibration parameter C16 (Pr. 919) to C19 (Pr. 920) (terminal 1 bias, gain torque)
Refer to page 288
Torque command value
400%
600%
1000%
1400%
-400%
Pr.805
,
Pr.806
settings
Torque command value
=
Pr.805
(or
Pr.806
)-1000%
Speed
Base speed
Torque
Pr. 803
= 1:
constant torque command
Pr. 803
= 0:
constant power command
(torque reduction)
Constant power range
Constant torque range