![Mitsubishi FR-A740-00023-EC Instruction Manual Download Page 169](http://html1.mh-extra.com/html/mitsubishi/fr-a740-00023-ec/fr-a740-00023-ec_instruction-manual_1809251169.webp)
159
Set V/F pattern
4
P
ARAME
T
E
R
S
4.10.4 Adjustable 5 points V/F (Pr. 71, Pr. 100 to Pr. 109)
A dedicated V/F pattern can be made by freely setting the V/F characteristic between a startup and the base
frequency and base voltage under V/F control (frequency voltage/frequency).
The torque pattern that is optimum for the machine's characteristic can be set.
Parameter
Number
Name
Initial Value
Setting Range
Description
71
Applied motor
0
0 to 8, 13 to 18,
20, 23, 24, 30, 33,
34, 40, 43, 44, 50,
53, 54
Set "2" for adjustable 5 points V/F
control.
100
V/F1(first frequency)
9999
0 to 400Hz, 9999
Set each points (frequency,
voltage) of V/F pattern.
9999: No V/F setting
101
V/F1(first frequency voltage)
0V
0 to 1000V
102
V/F2(second frequency)
9999
0 to 400Hz, 9999
103
V/F2(second frequency voltage)
0V
0 to 1000V
104
V/F3(third frequency)
9999
0 to 400Hz, 9999
105
V/F3(third frequency voltage)
0V
0 to 1000V
106
V/F4(fourth frequency)
9999
0 to 400Hz, 9999
107
V/F4(fourth frequency voltage)
0V
0 to 1000V
108
V/F5(fifth frequency)
9999
0 to 400Hz, 9999
109
V/F5(fifth frequency voltage)
0V
0 to 1000V
⋅
Any V/F characteristic can be provided by presetting the parameters of
V/F1 (first frequency voltage/first frequency) to V/F5
.
⋅
For a machine of large static friction coefficient and small dynamic
static friction coefficient, for example, set a V/F pattern that will
increase the voltage only in a low-speed range since such a machine
requires large torque at a start.
(Setting procedure)
1)Set the rated motor voltage in
Pr. 19 Base frequency voltage
. (No
function at the setting of "9999" (initial value) or "8888".)
2)Set
Pr. 71 Applied motor
to "2" (Adjustable 5 points V/F characteristic).
3)Set the frequency and voltage you want to set in
Pr. 100 to Pr. 109
.
CAUTION
⋅
Adjustable 5 points V/F characteristics function only under V/F control. They do not function under advanced magnetic flux
vector control, real sensorless vector control or vector control.
⋅
When
Pr. 19 Base frequency voltage
= "8888" or "9999",
Pr. 71
cannot be set to "2". To set
Pr. 71
to "2", set the rated voltage value in
Pr. 19
.
⋅
When the frequency values at each point are the same, a write disable error (
) appears.
⋅
Set the points (frequencies, voltages) of
Pr. 100 to Pr. 109
within the ranges of
Pr. 3 Base frequency
and
Pr. 19 Base frequency voltage
.
⋅
When "2" is set in
Pr. 71
,
Pr. 47 Second V/F (base frequency)
and
Pr. 113 Third V/F (base frequency)
will not function.
⋅
When
Pr. 71
is set to "2", the electronic thermal relay function makes calculation as a standard motor.
REMARKS
⋅
A greater energy saving effect can be expected by combining
Pr. 60 Energy saving control selection
and adjustable 5 points V/F.
⋅
For the 00170, 00250, the
Pr. 0 Torque boost
and
Pr. 12 DC injection brake operation voltage
settings are automatically changed
according to the
Pr. 71
setting as follows.
♦
Parameters referred to
♦
⋅
Pr. 3 Base frequency, Pr. 19 Base frequency voltage
Refer to page 153
⋅
Pr. 12 DC injection brake operation voltage
Refer to page 194
⋅
Pr. 47 Second V/F (base frequency)
,
Pr. 113 Third V/F (base frequency)
Refer to page 153
⋅
Pr. 60 Energy saving control selection
Refer to page 266
⋅
Pr. 71 Applied motor, Pr. 450 Second applied motor
Refer to page 179
⋅
Advanced magnetic flux vector control
Refer to page 140
⋅
Real sensorless vector control
Refer to page 87
⋅
Vector control
Refer to page 87
V/F
V/F
V/F
Base frequency
voltage
Pr.19
Base frequency
Pr.3
Torque boost
Pr.0
V/F Characteristic
0
V/F5
V/F4
V/F3
V/F2
V/F1
Frequency
Voltage
CAUTION
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
Pr. 71
Standard Motor Setting
0, 2, 3 to 8, 20, 23, 24, 40, 43, 44
Constant Torque Motor Setting
1, 13 to 18, 50, 53, 54
Pr. 0
3%
2%
Pr. 12
4%
2%