Selection and protection of a motor
4
P
ARAME
T
E
R
S
4.13.2 Applied motor (Pr. 71, Pr. 450)
(1) Set the motor to be used
Refer to the following list and set this parameter according to the motor used.
Setting of the used motor selects the thermal characteristic appropriate for the motor.
Setting is necessary when using a constant-torque motor. Thermal characteristic of the electronic thermal relay
function suitable for the motor is set.
When advanced magnetic flux vector, real sensorless vector control or vector control is selected, the motor
constants (SF-JR, SF-HR, SF-JRCA, SF-HRCA, SF-V5RU) necessary for control are selected as well.
Parameter
Number
Name
Initial Value
Setting Range
Description
71
Applied motor
0
0 to 8, 13 to 18, 20,
23, 24, 30, 33, 34,
40, 43, 44, 50, 53, 54
Selecting the standard motor or constant-
torque motor sets the corresponding motor
thermal characteristic.
450
Second applied motor
9999
0 to 8, 13 to 18, 20,
23, 24, 30, 33, 34,
40, 43, 44, 50, 53, 54
Set when using the second motor.
(same specifications as
Pr. 71
)
9999
Not function
Pr. 71 (Pr. 450)
Setting
Thermal Characteristic of the Electronic Thermal Relay
Function
Motor (
{
: used motor)
Pr. 71
Pr. 450
Standard
(SF-JR etc.)
Constant torque
(SF-JRCA etc.)
Vector
(SF-V5RU)
0
(
Pr. 71
initial value)
Thermal characteristics of a standard motor
1
Thermal characteristics of the Mitsubishi constant-torque motor
2
Thermal characteristics of a standard motor
Adjustable 5 points V/F
(Refer to page 159)
20
Mitsubishi standard motor (SF-JR 4P 1.5kW or less) thermal
characteristic for the constant-torque motor
30
Vector control dedicated motor (SF-V5RU)
40
Thermal characteristic of Mitsubishi high efficiency motor SF-HR
*1
50
Thermal characteristic of Mitsubishi constant-torque motor SF-HRCA
*2
3
Standard motor
Select "offline auto tuning
setting"
13
Constant-torque motor
23
Mitsubishi standard motor
(SF-JR 4P 1.5kW or less)
33
Vector control dedicated motor
(SF-V5RU, SF-THY)
43
Mitsubishi High efficiency motor
(SF-HR)
*1
53
Mitsubishi constant-torque motor
(SF-HRCA)
*2
4
Standard motor
Auto tuning data can be read,
changed, and set
14
Constant-torque motor
24
Mitsubishi standard motor
(SF-JR 4P 1.5kW or less)
34
Vector control dedicated motor
(SF-V5RU, SF-THY)
44
Mitsubishi High efficiency motor
(SF-HR)
*1
54
Mitsubishi constant-torque motor
(SF-HRCA)
*2
5
Standard motor
Star
connection
Direct input of
motor
constants is
enabled
15
Constant-torque motor
6
Standard motor
Delta
connection
16
Constant-torque motor
7
Standard motor
Star
connection
Motor
constants
direct input
+
offline auto
tuning
17
Constant-torque motor
8
Standard motor
Delta
connection
18
Constant-torque motor
—
9999
(initial
value)
Without second applied motor
*1
Motor constants of Mitsubishi high efficiency motor SF-HR.
*2
Motor constants of Mitsubishi constant-torque motor SF-HRCA.