161
Frequency setting by external terminals
4
P
ARAME
T
E
R
S
CAUTION
⋅
Changing the terminal assignment using
Pr. 178
to
Pr. 189 (input terminal function selection)
may affect the other functions. Make
setting after confirming the function of each terminal.
♦
Parameters referred to
♦
Pr. 15 Jog frequency
Refer to page 162
Pr. 28 Multi-speed input compensation selection
Refer to page 164
Pr. 59 Remote function selection
Refer to page 164
Pr. 79 Operation mode selection
Refer to page 301
Pr. 178 to Pr. 189 (input terminal function selection)
Refer to page 222
Multi-Speed Operation
Connection Example
10
2
5
Inverter
STF
REX
RH
RM
RL
Multi-speed selection
Frequency setting
potentiometer
Forward
rotation
PC
REMARKS
⋅
The priorities of the frequency commands by the external signals are
"jog operation > multi-speed operation > terminal 4 analog input >
terminal 2 analog input". (Refer to
page 282
for the frequency
command by analog input)
⋅
Valid in external operation mode or PU/external combined operation
mode (
Pr. 79
= "3" or "4").
⋅
Multi-speed parameters can also be set in the PU or external
operation mode.
⋅
Pr. 24 to Pr. 27
and
Pr. 232 to Pr. 239
settings have no priority between them.
⋅
When a value other than “0” is set in
Pr. 59 Remote function selection
,
the RH, RM and RL signals are used as the remote setting signals
and the multi-speed setting becomes invalid.
⋅
When making analog input compensation, set "1" in
Pr. 28 Multi-speed
input compensation selection
.