Selection and protection of a motor
4
P
ARAME
T
E
R
S
•
To enter the
Pr. 92
and
Pr. 93
motor constants in [mH]
<Operating procedure>
1) Set
Pr. 71
according to the motor used.
*1 For other settings of
Pr. 71
, refer to the
page 179
.
2) In the parameter setting mode, read the following parameters and set desired values.
Calculate the
Pr. 94
value from the following formula.
3)Refer to the following table and set
Pr. 83
and
Pr. 84
.
Motor
Pr.71
Setting
*
Mitsubishi standard
motor
Mitsubishi high
efficiency motor
SF-JR
0
SF-JR 4P 1.5kW or less
20
SF-HR
40
Mitsubishi constant-
torque motor
SF-JRCA 4P
SF-TH (constant torque)
1
SF-HRCA 4P
50
Vector control
dedicated motor
SF-V5RU
30
Pr. 94
setting = (1 -
M
2
)
×
100 (%)
L1
×
L2
Motor equivalent circuit diagram
Parameter
Number
Name
Setting Range
Setting
Increments
Initial
Value
82
Motor excitation current
(no load current)
01800 or less
0 to 500A, 9999
0.01A
9999
02160 or more
0 to 3600A, 9999
0.1A
90
Motor constant (R1)
01800 or less
0 to 50
Ω
, 9999
0.001
Ω
9999
02160 or more
0 to 400m
Ω
, 9999
0.01m
Ω
91
Motor constant (R2)
01800 or less
0 to 50
Ω
, 9999
0.001
Ω
9999
02160 or more
0 to 400m
Ω
, 9999
0.01m
Ω
92
Motor constant (L1)
01800 or less
0 to 1000mH, 9999
0.1mH
9999
02160 or more
0 to 400mH, 9999
0.01mH
93
Motor constant (L2)
01800 or less
0 to 1000mH, 9999
0.1mH
9999
02160 or more
0 to 400mH, 9999
0.01mH
94
Motor constant (X)
01800 or less
0 to 100%, 9999
0.1%
9999
02160 or more
0 to 100
%
, 9999
0.01%
859
Torque current
01800 or less
0 to 500A, 9999
0.01A
9999
02160 or more
0 to 3600A, 9999
0.1A
Parameter
Number
Name
Setting Range
Setting
Increments
Initial
Value
83
Motor rated voltage
0 to 1000V
0.1V
400V
84
Rated motor frequency
10 to 120Hz
0.01Hz
50Hz
REMARKS
· When "9999" is set in
Pr. 82
,
Pr. 90 to Pr. 94
,
Pr. 859
, Mitsubishi motor (SF-JR, SF-HR,SF-JRCA, SF-HRCA, SF-V5RU)
constants are used.
L1= I1+ M: Primary inductance
L2= I2+ M: Secondary inductance
M
V
R2/S
R1
I1
I2
R1: Primary resistance
I1: Primary leakage inductance
I2: Secondary leakage inductance
M: Excitation inductance
S: Slip
R2: Secondary resistance