343
Communication operation and setting
4
P
ARAME
T
E
R
S
Parameter
Parameters Register
Parameter Name
Read/Write
Remarks
0 to 999
41000 to
41999
Refer to the parameter list
(page 65)
for
the parameter names.
Read/write
The parameter 41000 is the
register number.
C2(902)
41902
Terminal 2 frequency setting bias
(frequency)
Read/write
C3(902)
42092
Terminal 2 frequency setting bias
(analog value)
Read/write
The analog value (%) set to
C3 (902)
is
read.
43902
Terminal 2 frequency setting bias
(terminal analog value)
Read
The analog value (%) of the voltage (current)
applied to the terminal 2 is read.
125(903)
41903
Terminal 2 frequency setting gain
(frequency)
Read/write
C4(903)
42093
Terminal 2 frequency setting gain
(analog value)
Read/write
The analog value (%) set to
C4 (903)
is
read.
43903
Terminal 2 frequency setting gain
(terminal analog value)
Read
The analog value (%) of the voltage
(current) applied to the terminal 2 is read.
C5(904)
41904
Terminal 4 frequency setting bias
(frequency)
Read/write
C6(904)
42094
Terminal 4 frequency setting bias
(analog value)
Read/write
The analog value (%) set to
C6 (904)
is
read.
43904
Terminal 4 frequency setting bias
(terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
126(905)
41905
Terminal 4 frequency setting gain
(frequency)
Read/write
C7(905)
42095
Terminal 4 frequency setting gain
(analog value)
Read/write
The analog value (%) set to
C7 (905)
is
read.
43905
Terminal 4 frequency setting gain
(terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
C8(930)
41930
Current output bias signal
Read/write
C9(930)
42120
Current output bias current
Read/write
C10(931)
41931
Current output gain signal
Read/write
C11(931)
42121
Current output gain current
Read/write
C12(917)
41917
Terminal 1 bias frequency (speed)
Read/write
C13(917)
42107
Terminal 1 bias (speed)
Read/write
Analog value (%) set in
C13 (917)
is read.
43917
Terminal 1 bias (speed)
(terminal analog value)
Read
Analog value (%) of the voltage applied to
terminal 1 is read.
C14(918)
41918
Terminal 1 gain frequency (speed)
Read/write
C15(918)
42108
Terminal 1 gain (speed)
Read/write
Analog value (%) set in
C15 (918)
is read.
43918
Terminal 1 gain (speed)
(terminal analog value)
Read
Analog value (%) of the voltage applied to
terminal 1 is read.
C16(919)
41919
Terminal 1 bias command (torque/
magnetic flux)
Read/write
C17(919)
42109
Terminal 1 bias (torque/magnetic flux)
Read/write
Analog value (%) set in
C17 (919)
is read.
43919
Terminal 1 bias (torque/magnetic flux)
(terminal analog value)
Read
Analog value (%) of the voltage applied to
terminal 1 is read.
C18(920)
41920
Terminal 1 gain command (torque/
magnetic flux)
Read/write
C19(920)
42110
Terminal 1 gain (torque/magnetic flux)
Read/write
Analog value (%) set in
C19 (920)
is read.
43920
Terminal 1 gain (torque/magnetic flux)
(terminal analog value)
Read
Analog value (%) of the voltage applied to
terminal 1 is read.
C38(932)
41932
Terminal 4 bias command (torque/
magnetic flux)
Read/write
C39(932)
42122
Terminal 4 bias (torque/magnetic flux)
Read/write
Analog value (%) set in
C39 (932)
is read.
43932
Terminal 4 bias (torque/magnetic flux)
(terminal analog value)
Read
Analog value (%) of the current (voltage)
applied to terminal 4 is read.
C40(933)
41933
Terminal 4 gain command (torque/
magnetic flux)
Read/write
C41(933)
42123
Terminal 4 gain (torque/magnetic flux)
Read/write
Analog value (%) set in
C41 (933)
is read.
43933
Terminal 4 gain (torque/magnetic flux)
(terminal analog value)
Read
Analog value (%) of the current (voltage)
applied to terminal 4 is read.