![Mitsubishi FR-A740-00023-EC Instruction Manual Download Page 263](http://html1.mh-extra.com/html/mitsubishi/fr-a740-00023-ec/fr-a740-00023-ec_instruction-manual_1809251263.webp)
253
Monitor display and monitor output signal
4
P
ARAME
T
E
R
S
(3) How to calibrate the terminal CA when using the operation panel (FR-DU07)
REMARKS
⋅
Calibration can also be made for external operation. Set the frequency in external operation mode, and make calibration in the
above procedure.
⋅
Calibration can be made even during operation.
⋅
For the operation procedure using the parameter unit (FR-PU04/FR-PU07), refer to the parameter unit instruction manual.
♦
Parameters referred to
♦
Pr. 54 CA terminal function selection
Refer to page 244
Pr. 55 Frequency monitoring reference
Refer to page 249
Pr. 56 Current monitoring reference
Refer to page 249
Pr. 158 AM terminal function selection
Refer to page 244
Press to return to the indication (step 4).
9.
Press . Setting is complete.
2.
Press to choose the parameter
setting mode.
3.
Turn until appears.
Flicker...Parameter setting complete!!
1.
Confirmation of the RUN indication and
operation mode indication
4.
Press to display .
6.
Press to enable setting.
7.
If the inverter is at a stop, (press
or ) to start the inverter.
(Motor needs not be connected.)
8.
Turn to adjust the indicator needle
to the desired position.
By turning , you can read another parameter.
(When Pr. 54=1)
Press twice to show the next parameter ( ).
Display
Operation
( )
+
‑
The parameter
number read
previously appears.
C0 to C41
setting
is enabled.
Analog indicator
5.
Turn until appears.
Set to
C0 CA terminal calibration
.
The monitor set to
Pr. 54
CA terminal
function selection
is displayed.
Summary of Contents for FR-A740-00023-EC
Page 58: ...48 MEMO...
Page 70: ...60 MEMO...
Page 400: ...390 MEMO...
Page 450: ...440 MEMO...
Page 473: ...463 MEMO...