349
Special operation and frequency control
4
P
ARAME
T
E
R
S
(1) PID control basic configuration
⋅
Pr. 128
= "10, 11" (Deviation value signal input)
⋅
Pr. 128
= "20, 21" (Measured value input)
131
PID upper limit
9999
0 to 100%
Set the maximum value. If the feedback value exceeds the
setting, the FUP signal is output. The maximum input (20mA/
5V/10V) of the measured value (terminal 4) is equivalent to
100%.
9999
No function
132
PID lower limit
9999
0 to 100%
Set the minimum value. If the measured value falls below the
setting range, the FDN signal is output. The maximum input
(20mA/5V/10V) of the measured value (terminal 4) is
equivalent to 100%.
9999
No function
133
*1
PID action set point
9999
0 to 100%
Used to set the set point for PID control.
9999
Terminal 2 input is the set point.
134
*1
PID differential time
9999
0.01 to
10.00s
For deviation lamp input, time (Td) required for providing only
the manipulated variable for the proportional (P) action. As the
differential time increases, greater response is made to a
deviation change.
9999
No differential control
575
Output interruption
detection time
1s
0 to 3600s
The inverter stops operation if the output frequency after PID
operation remains at less than the
Pr. 576
setting for longer
than the time set in
Pr. 575
.
9999
Without output interruption function
576
Output interruption
detection level
0Hz
0 to 400Hz
Set the frequency at which the output interruption processing
is performed.
577
Output interruption
cancel level
1000% 900 to 1100%
Set the level (
Pr. 577
minus 1000%) at which the PID output
interruption function is canceled.
*1
Pr. 129, Pr. 130, Pr. 133
and
Pr. 134
can be set during operation. They can also be set independently of the operation mode.
*2
For details, refer to
the FR-A700 PLC FUNCTION PROGRAM MANUAL
.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
+-
IM
Deviation signal
Feedback signal (measured value)
Ti S
1
1+
+Td S
Kp
PID operation
To outside
Set point
Inverter circuit
Motor
Terminal 1
0 to 10VDC
(0 to 5V)
Kp: Proportionality constant Ti: Integral time S: Operator Td: Differential time
Manipulated
variable
+-
IM
Ti
S
Kp 1+ +Td S
1
PID operation
Pr. 133
or
terminal 2
Set point
Inverter circuit
Motor
Feedback signal (measured value)
Terminal 4
Kp: Proportionality constant Ti: Integral time S: Operator Td: Differential time
Manipulated
variable
0 to 5VDC
(0 to 10V, 4 to 20mA)
4 to 20mADC (0 to 5V, 0 to 10V)