Selection and protection of a motor
(4) Tune second applied motor
· When you want to switch two motors with one inverter, set the second motor in
Pr. 450 Second applied motor
.(Initial
setting is without second applied motor.
(Refer to page 179)
)
Perform tuning using
Pr. 574 Second motor online auto tuning
.
Pr. 574 Second motor online auto tuning
is made valid when the RT signal turns on.
Parameter
Number
Description
51
Used as rated motor current and electronic thermal relay
parameters.
450
Applied motor
453
Motor capacity (down to one rank lower than the inverter
capacity, note that the capacity should be 0.4kW or more)
454
Number of motor poles
REMARKS
· The RT signal acts as the second function selection signal and makes the other second functions valid.
(Refer to page 226.)
The RT signal is assigned to the terminal RT in the initial setting. By setting "3" in any of
Pr. 178 to Pr. 189 (input terminal function
selection)
, you can assign the RT signal to the other terminal.
CAUTION
· Changing the terminal assignment using
Pr. 178 to Pr. 189 (input terminal function selection)
may affect the other functions. Make
setting after confirming the function of each terminal.
♦
Parameters referred to
♦
Pr. 9 Electronic thermal O/L relay
Refer to page 175
Pr. 71 Applied motor
Refer to page 179
Pr. 80 Motor capacity
Refer to page 87
Pr. 81 Number of motor poles
Refer to page 87
Pr. 96 Auto tuning setting/status
Refer to page 181
Pr. 178 to Pr. 189 (input terminal function selection)
Refer to page 222
Pr. 190 to Pr .196 (output terminal function selection)
Refer to page 230