II
Restrictions ]
- 18 -
HWE07010
GB
(2) High COP combinations
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
Outdoor
units
Composing units
Maximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable in-
door units
200
-
-
-
100 - 260
17
P15 - P200 models
R410A series indoor units
300
-
-
-
150 - 390
26
400
200
200
-
200 - 520
34
P15 - P500 models
R410A series indoor units
450
250
200
-
225 - 585
39
500
300
200
-
250 - 650
43
550
300
250
-
275 - 715
47
600
300
300
-
300 - 780
50
650
350
300
-
325 - 845
700
300
200
200
350 - 910
750
300
250
200
375 - 975
800
300
300
200
400 - 1040
850
300
300
250
425 - 1105
900
300
300
300
450 - 1170
Summary of Contents for PUHY-(E)P300
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 57: ... 48 ...
Page 67: ... 58 ...
Page 75: ... 66 ...
Page 77: ... 68 ...
Page 81: ... 72 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 113: ... 104 ...
Page 115: ... 106 ...
Page 163: ... 154 ...
Page 255: ... 246 ...
Page 257: ... 248 ...