Troubleshooting ]
- 177 -
HWE07010
GB
1. Error
Code
Overcurrent error due to short-circuited motor (Detail code 105)
2. Error
definition and error detection method
When a short is detected on the load side just before starting the inverter operation.
3. Cause, Check method and remedy
In the case of 4250
In the case of 4255
Refer to section - 6 - "Inverter" under part [4] "Trouble shooting principal parts" for error codes related to the
inverter.(page 232)
1. Error
Code
Heatsink overheat protection before startup
2. Error
definition and error detection method
The heatsink temperature (THHS) remains at or above 100°C [212°F] for 10 minutes or more at inverter startup.
3. Cause, check method and remedy
Same as 4230 error
4250
4255
Cause
Check method and remedy
(1)
Short - circuited compressor
Refer to 9 [4] - 6 - (2) [2].(page 234)
(2)
Output wiring
Check for a short circuit.
Cause
Check method and remedy
(1)
Short - circuited fan motor
Refer to 9 [4] - 6 - (2) [5].(page 235)
(2)
Output wiring
Check for a short circuit.