[
VIII
Test Run Mode ]
- 116 -
HWE07010
GB
Operation
Outdoor unit model
PUHY-P300YHM-A
PUHY-P350YHM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/19°C [81°F/66°F]
27°C/19°C [81°F/66°F]
Outdoor
35°C/ - [95°F/ - ]
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
3
3
No. of units in opera-
tion
3
3
Model
-
100/100/100
100/125/125
Piping
Main pipe
m [ft]
5 [16-3/8 ]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
10 [32-3/4 ]
Total pipe length
35 [114-13/16 ]
35 [114-13/16 ]
Fan speed
-
Hi
Hi
Amount of refrigerant
kg
[lbs-oz]
15 [33]
15 [33]
Outdoor
unit
Electric current
A
14.5
17.9
Voltage
V
400
400
Compressor frequency
Hz
74
95
LEV open-
ing
Indoor unit
Pulse
325/325/325
325/387/387
SC (LEV1)
100
100
LEV2
-
-
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.95/0.84 [428/122]
2.86/0.76 [415/110]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
84 [183]
90 [194]
Heat exchanger out-
let (TH3)
44 [111]
43 [109]
Accumulator inlet
7 [45]
7 [45]
Accumulator outlet
7 [45]
7 [45]
SCC outlet (TH6)
22 [72]
22 [72]
Compressor inlet
19 [66]
19 [66]
Compressor shell
bottom
42 [108]
42 [108]
Indoor
unit
LEV inlet
19 [66]
19 [66]
Heat exchanger
outlet
6 [43]
6 [43]
Summary of Contents for PUHY-(E)P300
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 57: ... 48 ...
Page 67: ... 58 ...
Page 75: ... 66 ...
Page 77: ... 68 ...
Page 81: ... 72 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 113: ... 104 ...
Page 115: ... 106 ...
Page 163: ... 154 ...
Page 255: ... 246 ...
Page 257: ... 248 ...