[
VIII
Test Run Mode ]
- 146 -
HWE07010
GB
(2) Heating operation
Operation
Outdoor unit model
PUHY-P950YSHM-A
PUHY-P250YHM-A
PUHY-P300YHM-A
PUHY-P400YHM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/ - [68°F/ - ]
Outdoor
7°C/6°C [45°F/43°F]
Indoor
unit
No. of connected
units
Unit
8
No. of units in opera-
tion
8
Model
-
250/200/200/125/100/32/32/25
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
85 [278-13/16]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
42 [ 93 ]
Outdoor
unit
Electric current
A
48.1
Voltage
V
400
Compressor frequency
Hz
72
90
90
LEV open-
ing
Indoor unit
Pulse
400/332/332/406/332/254/254/229
SC (LEV1)
0
LEV2
1400
1400
1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.95/0.62
2.90/0.62
2.91/0.60
[428/90]
[421/90]
[422/87]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
81 [ 178 ]
82 [ 180 ]
89 [ 192 ]
Heat exchanger out-
let (TH3)
-3 [ 26 ]
-3 [ 26 ]
-4 [ 25 ]
Accumulator inlet
-3 [ 26 ]
-3 [ 26 ]
-4 [ 25 ]
Accumulator outlet
-3 [ 26 ]
-3 [ 26 ]
-4 [ 25 ]
Compressor inlet
-3 [ 26 ]
-3 [ 26 ]
-4 [ 25 ]
Compressor shell
bottom
30 [ 86 ]
30 [ 85 ]
40 [ 104 ]
Indoor
unit
LEV inlet
39 [ 102 ]
Heat exchanger
outlet
80 [ 176 ]
Summary of Contents for PUHY-(E)P300
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 57: ... 48 ...
Page 67: ... 58 ...
Page 75: ... 66 ...
Page 77: ... 68 ...
Page 81: ... 72 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 113: ... 104 ...
Page 115: ... 106 ...
Page 163: ... 154 ...
Page 255: ... 246 ...
Page 257: ... 248 ...