IX
Troubleshooting ]
- 182 -
HWE07010
GB
1. Error
Code
IPM open/ACCT erroneous wiring (Detail code 119)
2. Error
definition and error detection method
Presence of enough current cannot be detected during the self-diagnostic operation immediately before inverter startup.
3. Cause, check method and remedy
Refer to section - 6 -"Inverter" under part [4] "Trouble shootiong principal parts" for error codes related to the
inverter.(page 232)
1. Error
Code
ACCT faulty wiring detection (Detail code 120)
2. Error
definition and error detection method
Presence of target current cannot be detected during the self-diagnostic operation immediately before startup. (Detection of
improperly mounted ACCT sensor)
3. Cause, check method and remedy
Refer to section - 6 - "Inverter" under part [4] "Trouble shooting principal parts" for error codes related to the
inverter.(page 232)
5301
Cause
Check method and remedy
(1)
Inverter output wiring problem
Check output wiring connections.
Confirm that the U- and W-phase output cables are put through CT12
and CT22 on the inverter board respectively.
(2)
Inverter failure
Refer to 9 [4]-6-(2) [3], [4].(page 235)
(3)
Compressor failure
Refer to 9 [4]-6-(2) [2].(page 234)
5301
Cause
Check method and remedy
(1)
Inverter output wiring problem
Check output wiring connections.
Confirm that the U- and W-phase output cables are put through CT12
and CT22 on the inverter board respectively.
(2)
Inverter failure
Refer to 9 [4]-6-(2) [3], [4].(page 235)
(3)
Compressor failure
Refer to 9 [4]-6-(2) [2].(page 234)
Summary of Contents for PUHY-(E)P300
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 57: ... 48 ...
Page 67: ... 58 ...
Page 75: ... 66 ...
Page 77: ... 68 ...
Page 81: ... 72 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 113: ... 104 ...
Page 115: ... 106 ...
Page 163: ... 154 ...
Page 255: ... 246 ...
Page 257: ... 248 ...