VIII
Test Run Mode ]
- 130 -
HWE07010
GB
(2) Heating operation
Operation
Outdoor unit model
PUHY-P500YSHM-A
PUHY-P250YHM-A
PUHY-P250YHM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/ - [68°F/ - ]
Outdoor
7°C/ 6°C [45°F/43°F]
Indoor
unit
No. of connected
units
Unit
4
No. of units in opera-
tion
4
Model
-
125/125/125/125
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
45 [147-5/8]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
22 [49]
Outdoor
unit
Electric current
A
26.3
Voltage
V
400
Compressor frequency
Hz
71
71
LEV open-
ing
Indoor unit
Pulse
406/406/406/406
SC (LEV1)
0
LEV2
1400
1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.81/0.66 [408/96]
2.81/0.66 [408/96]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
82 [180]
82 [180]
Heat exchanger out-
let (TH3)
-2 [28]
-2 [28]
Accumulator inlet
-2 [28]
-2 [28]
Accumulator outlet
-2 [28]
-2 [28]
Compressor inlet
-2 [28]
-2 [28]
Compressor shell
bottom
40 [104]
40 [104]
Indoor
unit
LEV inlet
37 [99]
Heat exchanger
outlet
80 [176]
Summary of Contents for PUHY-(E)P300
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 57: ... 48 ...
Page 67: ... 58 ...
Page 75: ... 66 ...
Page 77: ... 68 ...
Page 81: ... 72 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 113: ... 104 ...
Page 115: ... 106 ...
Page 163: ... 154 ...
Page 255: ... 246 ...
Page 257: ... 248 ...