IX
Troubleshooting ]
- 178 -
HWE07010
GB
1. Error
Code
Suction temperature sensor failure (indoor unit)
Liquid pipe temperature sensor failure (indoor unit)
Gas pipe temperature sensor failure (indoor unit)
Outdoor air temperature sensor failure (indoor unit)
2. Error
definition and error detection method
If a short or an open is detected during thermostat ON, the outdoor unit turns to anti-restart mode for 3 minutes. When the
error is not restored after 3 minutes (if restored, the outdoor unit runs normally), the outdoor unit makes an error stop.
Short: detectable at 90°C [194°F] or higher
Open: detectable at -40°C [-40°F] or lower
Sensor error at gas-side cannot be detected under the following conditions.
∗
During heating operation
∗
During cooling operation for 3 minutes after the compressor turns on.
3. Cause, check method and remedy
1. Error
Code
Outdoor air temperature sensor failure (OA processing unit)
2. Cause, check method and remedy
5101
5102
5103
5104
Cause
Check method and remedy
(1)
Thermistor failure
Check the thermistor resistor.
0°C [32°F]: 15 kohm
10°C [50°F]: 9.7 kohm
20°C [68°F] : 6.4 kohm
30°C [86°F] : 4.3 kohm
40°C [104°F] : 3.1 kohm
(2)
Connector contact failure
(3)
Disconnected wire or partial disconnected
thermistor wire
(4)
Unattached thermistor or contact failure
(5)
Indoor board (detection circuit) failure
Check the connector contact.
When no fault is found, the indoor board is a failure.
5104
Cause
Check method and remedy
(1)
The connector (CN29) is not connected tightly.
Check the contact of the connector.
(2)
The outdoor air temperature sensor is broken.
Replace the sensor.
Summary of Contents for PUHY-(E)P300
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 57: ... 48 ...
Page 67: ... 58 ...
Page 75: ... 66 ...
Page 77: ... 68 ...
Page 81: ... 72 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 113: ... 104 ...
Page 115: ... 106 ...
Page 163: ... 154 ...
Page 255: ... 246 ...
Page 257: ... 248 ...