1. Error
Code
Abnormal low pressure
2. Error
definition and error detection method
When starting the compressor from Stop Mode for the first time if low pressure reads 0.098MPa [14psi] immediately
before start-up, the operation immediately stops.
3. Cause, check method and remedy
1301
Cause
Check method and remedy
(1)
Inner pressure drop due to a leakage.
Refer to the section on troubleshooting the low pressure
sensor.(page 223)
(2)
Low pressure sensor failure
(3)
Short-circuited pressure sensor cable due to
torn outer rubber
(4)
A pin on the male connector is missing.
(5)
Disconnected wire
(6)
Failure of the low pressure input circuit on the
controller board