VIII
Test Run Mode ]
- 135 -
HWE07010
GB
Operation
Outdoor unit model
PUHY-P750YSHM-A
PUHY-P350YHM-A
PUHY-P400YHM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/ - [68°F/ - ]
Outdoor
7°C/6°C [45°F/43°F]
Indoor
unit
No. of connected
units
Unit
6
No. of units in opera-
tion
6
Model
-
125/125/125/125/125/125
Piping
Main pipe
m [ft]
5 [16-3/8]
Branch pipe
10 [32-3/4]
Total pipe length
65 [213-1/4]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
34 [75]
Outdoor
unit
Electric current
A
40.8
Voltage
V
400
Compressor frequency
Hz
101
102
LEV open-
ing
Indoor unit
Pulse
332/332/406/406/406/406
SC (LEV1)
0
LEV2
1160
1280
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.90/0.62 [421/90]
2.91/0.60 [422/87]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
82 [180] 89 [192]
Heat exchanger out-
let (TH3)
-3 [26]
-4 [25]
Accumulator inlet
-3 [26]
-4 [25]
Accumulator outlet
-3 [26]
-4 [25]
Compressor inlet
-3 [26]
-4 [25]
Compressor shell
bottom
30 [85] 40 [104]
Indoor
unit
LEV inlet
39 [102]
Heat exchanger
outlet
80 [176]
Summary of Contents for PUHY-(E)P300
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 57: ... 48 ...
Page 67: ... 58 ...
Page 75: ... 66 ...
Page 77: ... 68 ...
Page 81: ... 72 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 113: ... 104 ...
Page 115: ... 106 ...
Page 163: ... 154 ...
Page 255: ... 246 ...
Page 257: ... 248 ...