IX
Troubleshooting ]
- 176 -
HWE07010
GB
1. Error
Code
Overcurrent breaker trip (Detail code 106,107)
2. Error
definition and error detection method
P200 and P250 models
Overcurrent 94 Apeak or 22 Arms and above is detected by the current sensor.
P300 models and above
Overcurrent 94 Apeak or 35 Arms and above is detected by the current sensor.
3. Cause, check method and remedy
Refer to section - 6 - "Inverter" under part [4] "Trouble shooting principal parts" for error codes related to the
inverter.(page 232)
1. Error
Code
IPM short/ grounding fault (Detail code 104)
2. Error
definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255
Refer to section - 6 - "Inverter" under part [4] "Trouble shooting principal parts" for error codes related to the
inverter.(page 232)
4250
4255
Cause
Check method and remedy
(1)
Inverter output related
Refer to 9 [4] - 6 - (2) [1] - [4].(page 234)
Check the IGBT module resistance value of the inverter board, if
no problems are found.
(Refer to the Trouble shooting for IGBT module)
4250
4255
Cause
Check method and remedy
(1)
Grounding fault compressor
Refer to 9 [4] - 6 - (2) [2].(page 234)
(2)
Inverter output related
Refer to 9 [4] - 6 - (2) [1]- [4].(page 234)
Cause
Check method and remedy
(1)
Grounding fault of fan motor
Refer to 9 [4] - 6 - (2) [5].(page 235)
(2)
Fan board failure
Refer to 9 [4] - 6 - (2) [6].(page 235)
Summary of Contents for PUHY-(E)P300
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 55: ... 46 ...
Page 57: ... 48 ...
Page 67: ... 58 ...
Page 75: ... 66 ...
Page 77: ... 68 ...
Page 81: ... 72 ...
Page 87: ... 78 ...
Page 89: ... 80 ...
Page 113: ... 104 ...
Page 115: ... 106 ...
Page 163: ... 154 ...
Page 255: ... 246 ...
Page 257: ... 248 ...