Appendix 5 Error Code List
CC-Link IE Field Network
*1 The error code '4807H' is stored to SD1452 if data is backed up and restored with any of the following combinations of modules.
⋅
Data backup for NZ2GF2B1N1-16D, and data restoration for NZ2GF2B1-16D or NZ2GF2B1N-16D
⋅
Data backup for NZ2GF2B1N1-16T, and data restoration for NZ2GF2B1-16T or NZ2GF2B1N-16T
⋅
Data backup for NZ2GF2B1N1-16TE, and data restoration for NZ2GF2B1-16TE or NZ2GF2B1N-16TE
Error code
Error and cause
Corrective action
Type/model name
BAD1H
Data restoration was performed
using backup data of module
that is different from module for
data restoration target.
Use the data that was backed up by using a module with the
same model name as one used for data restoration.
■
Basic Digital Input Module
• NZ2GF2B1-16D, NZ2GF2B1N-
16D, NZ2GF2B1N1-16D
NZ2GF2B2-16A, NZ2GF2B1-
32D
• NZ2GFCE3-16D, NZ2GFCE3-
16DE, NZ2GFCE3N-32D
• NZ2GFCM1-16D, NZ2GFCM1-
16DE
• NZ2GFCF1-32D
• NZ2GF2S2-16A
■
Basic Digital Output Module
• NZ2GF2B1-16T, NZ2GF2B1-
16TE, NZ2GF2B1N-16T,
NZ2GF2B1N-16TE,
NZ2GF2B1N1-16T
,
NZ2GF2B1N1-16TE
NZ2GF2B2-16R, NZ2GF2B2-
16S, NZ2GF2B1-32T,
NZ2GF2B1-32TE
• NZ2GFCE3-16T, NZ2GFCE3-
16TE, NZ2GFCE3N-32T
• NZ2GFCM1-16T, NZ2GFCM1-
16TE
• NZ2GFCF1-32T
• NZ2GF2S2-16R, NZ2GF2S2-
16S
■
Basic Digital I/O Combined
Module
• NZ2GF2B1-32DT, NZ2GF2B1-
32DTE
• NZ2GFCE3N-32DT
• NZ2GFCF1-32DT
■
Basic Analog Input Module
• NZ2GF2BN-60AD4
■
Basic Analog Output Module
• NZ2GF2BN-60DA4
■
High-Speed Counter Module
• NZ2GFCF-D62PD2
BAD2H
Data restoration was performed
using backup data of newer
module than module for data
restoration target.
Perform the data restoration function by using the data that was
backed up from a module with the same version or earlier than
one used for data restoration.
BAD3H
Corrupted backup data was
restored.
Use another backup data and retry.
BAD4H
Data backup was performed in
the state of being unable to
create backup data of module.
Non-volatile memory data (parameter) error occurred. Retry data
backup after removing the error.
BAD5H
An attempt was made to restore
data to a remote I/O module
when the automatic I/O
parameter setting is enabled.
Data cannot be restored to a remote I/O module when the
automatic I/O parameter setting is enabled.
Disable the automatic I/O parameter setting for the restoration
target remote I/O module.
■
Basic Digital Input Module
• NZ2GF2B1N1-16D, NZ2GFCF1-
32D
■
Basic Digital Output Module
• NZ2GF2B1N1-16T,
NZ2GF2B1N1-16TE,
NZ2GFCF1-32T
■
Basic Digital I/O Combined
Module
• NZ2GFCF1-32DT
Summary of Contents for 13JV28
Page 1: ...iQ Sensor Solution Reference Manual ...
Page 2: ......
Page 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Page 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Page 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Page 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Page 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Page 373: ...I 371 MEMO ...
Page 377: ......