APPX
Appendix 5 Error Code List
349
A
Panasonic Industrial Devices SUNX Co., Ltd.
Error code
Error and cause
Corrective action
Type/model name
4805H
The data backup/restoration
function was performed for the
device which is not supported by
the data backup/restoration
function of iQ Sensor Solution.
The data backup/restoration function is not supported by SC-
T1JA, SC-A01, and SC-A02.
Perform the data backup/restoration function for the device which
is supported by the data backup/restoration function of iQ Sensor
Solution.
■
Analog input unit
• SC-T1JA
• SC-A01
• SC-A02
4805H
The end unit is not recognized
because the end unit is not
attached to the sensor amplifier
properly.
Check if the end unit unconnected flag (for one-station occupied
operation: 15th bit of RWr0, for four-station occupied operation:
RX1F) is not set.
Check if the end unit is attached to the sensor amplifier properly.
■
Digital fiber sensor
• FX-301
• FX-305
• FX-501
• FX-502
E0C4H
Data backup/restoration
function was performed for the
station sub-ID to which the
sensor amplifier is not
connected.
Check that the sensor amplifier is connected properly, and
perform data backup/restoration function to the connected station
sub-ID.
E0C5H
Data backup failed because the
end unit is not attached to the
sensor amplifier properly.
Check if the end unit is attached to the sensor amplifier properly,
and perform data backup again.
E0C6H
Data restoration failed because
the end unit is not attached to
the sensor amplifier properly or
the specified backup data is not
correct.
Check if the end unit is attached to the sensor amplifier properly
or the specified backup data is correct. Then perform the data
restoration again.
4805H
The end unit is not recognized
because the end unit is not
attached to the sensor amplifier
properly.
Check if the end unit unconnected flag (for one-station occupied
operation: 15th bit of RWr0, for four-station occupied operation:
RX1F) is not set.
Check if the end unit is attached to the sensor amplifier properly.
■
Digital laser sensor
• LS-403
E0C4H
Data backup/restoration
function was performed for the
station sub-ID to which the
sensor amplifier is not
connected.
Check that the sensor amplifier is connected properly, and
perform data backup/restoration function to the connected station
sub-ID.
E0C5H
Data backup failed because the
end unit is not attached to the
sensor amplifier properly.
Check if the end unit is attached to the sensor amplifier properly,
and perform data backup again.
E0C6H
Data restoration failed because
the end unit is not attached to
the sensor amplifier properly or
the specified backup data is not
correct.
Check if the end unit is attached to the sensor amplifier properly
or the specified backup data is correct. Then perform the data
restoration again.
4805H
The end unit is not recognized
because the end unit is not
attached to the sensor amplifier
properly.
Check if the end unit unconnected flag (for one-station occupied
operation: 15th bit of RWr0, for four-station occupied operation:
RX1F) is not set.
Check if the end unit is attached to the sensor amplifier properly.
■
Head-separated dual display
digital pressure sensor
• DPS-401
• DPS-402
E0C4H
Data backup/restoration
function was performed for the
station sub-ID to which the
sensor amplifier is not
connected.
Check that the sensor amplifier is connected properly, and
perform data backup/restoration function to the connected station
sub-ID.
E0C5H
Data backup failed because the
end unit is not attached to the
sensor amplifier properly.
Check if the end unit is attached to the sensor amplifier properly,
and perform data backup again.
E0C6H
Data restoration failed because
the end unit is not attached to
the sensor amplifier properly or
the specified backup data is not
correct.
Check if the end unit is attached to the sensor amplifier properly
or the specified backup data is correct. Then perform the data
restoration again.
Summary of Contents for 13JV28
Page 1: ...iQ Sensor Solution Reference Manual ...
Page 2: ......
Page 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Page 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Page 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Page 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Page 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Page 373: ...I 371 MEMO ...
Page 377: ......