APPX
Appendix 4 Considerations for Using Device Supporting iQSS
345
A
CC-Link IE Field Network
Mitsubishi Electric Corporation
■
List of combinations of modules for data backup and for data restoration
Type/model name
Function
Consideration
■
Basic Digital Input Module
• NZ2GF2B1-16D, NZ2GF2B1N-
16D, NZ2GF2B1N1-16D,
NZ2GF2B2-16A, NZ2GF2B1-
32D
• NZ2GFCE3-16D, NZ2GFCE3-
16DE, NZ2GFCE3N-32D
• NZ2GFCM1-16D, NZ2GFCM1-
16DE
• NZ2GFCF1-32D
• NZ2GF2S2-16A
■
Basic Digital Output Module
• NZ2GF2B1-16T, NZ2GF2B1-
16TE, NZ2GF2B1N-16T,
NZ2GF2B1N-16TE,
NZ2GF2B1N1-16T,
NZ2GF2B1N1-16TE,
NZ2GF2B2-16R, NZ2GF2B2-
16S, NZ2GF2B1-32T,
NZ2GF2B1-32TE
• NZ2GFCE3-16T, NZ2GFCE3-
16TE, NZ2GFCE3N-32T
• NZ2GFCM1-16T, NZ2GFCM1-
16TE
• NZ2GFCF1-32T
• NZ2GF2S2-16R, NZ2GF2S2-
16S
■
Basic Digital I/O Combined
Module
• NZ2GF2B1-32DT, NZ2GF2B1-
32DTE
• NZ2GFCE3N-32DT
• NZ2GFCF1-32DT
■
Basic Analog Input Module
• NZ2GF2BN-60AD4
■
Basic Analog Output Module
• NZ2GF2BN-60DA4
■
High-Speed Counter Module
• NZ2GFCF-D62PD2
Data backup/restoration
When data backup/restoration failed, an error code is stored to SD1453.
Check the error code and take corrective actions. (
List, or
User's manual for data backup/restoration target modules)
Check that the restoration target module operates normally after performing
the data restoration.
When an error occurs on the restoration target module, check the error code
and take corrective actions. (
User's manual for data backup/restoration
target modules)
Backup data (parameter) cannot be restored to a module whose model name
is different from the one used for data backup.
However, it can be restored to a module having a compatibility of functions
even if its model name is different from the one used for data backup.
For details, check the following table 'List of combinations of modules for data
backup and for data restoration'.
Module for data backup
Module for data restoration
NZ2GF2B1-16D
NZ2GF2B1-16D, NZ2GF2B1N-16D, NZ2GF2B1N1-16D
NZ2GF2B1-16T
NZ2GF2B1-16T, NZ2GF2B1N-16T, NZ2GF2B1N1-16T
NZ2GF2B1-16TE
NZ2GF2B1-16TE, NZ2GF2B1N-16TE, NZ2GF2B1N1-16TE
NZ2GF2B1N-16D
NZ2GF2B1N-16D, NZ2GF2B1N1-16D
NZ2GF2B1N-16T
NZ2GF2B1N-16T, NZ2GF2B1N1-16T
NZ2GF2B1N-16TE
NZ2GF2B1N-16TE, NZ2GF2B1N1-16TE
NZ2GF2B1-32D, NZ2GF2B1-32DT, NZ2GF2B1-32DTE
Only a module with the same model name as one used for data backup can
be used for data restoration.
NZ2GF2B1-32T, NZ2GF2B1-32TE
NZ2GF2B1N1-16D, NZ2GF2B1N1-16T, NZ2GF2B1N1-16TE
NZ2GF2B2-16A, NZ2GF2B2-16R, NZ2GF2B2-16S
NZ2GFCE3-16D, NZ2GFCE3-16DE, NZ2GFCE3-16T, NZ2GFCE3-16TE
NZ2GFCE3N-32D, NZ2GFCE3N-32DT, NZ2GFCE3N-32T
NZ2GFCM1-16D, NZ2GFCM1-16DE, NZ2GFCM1-16T, NZ2GFCM1-16TE
NZ2GFCF1-32D, NZ2GFCF1-32T, NZ2GFCF1-32DT
NZ2GF2S2-16A, NZ2GF2S2-16R, NZ2GF2S2-16S
NZ2GF2BN-60AD4, NZ2GF2BN-60DA4, NZ2GFCF-D62PD2
Summary of Contents for 13JV28
Page 1: ...iQ Sensor Solution Reference Manual ...
Page 2: ......
Page 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Page 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Page 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Page 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Page 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Page 373: ...I 371 MEMO ...
Page 377: ......