300
10 Ethernet
10.5 Backing up/Restoring Data of Devices Supporting iQSS
Program execution for data restoration
Information in an SD memory card can be restored to a device supporting iQSS.
Select a backup folder to be restored. In the data restoration, information such as a model name or device version in the
system file ($BKUP_UNIT_INF.BSI) created with backup is compared with that of a device supporting iQSS. If the information
is mismatched, a restoration error will occur.
Data backup and restoration can be performed regardless of the operating status of a CPU module.
The following shows the procedure to restore data with a program.
For details on special relays (SM) and special registers (SD) to be used and their setting ranges, refer to the
following section.
Page 355 Special Relay (SM)/Special Register (SD) List
Results of the data backup and restoration functions can be checked in the event history of an engineering
tool. (
Execution method of data restoration
Special relays (SM) and special registers (SD) are used for data restoration.
■
Acquiring a right to use
To prevent the same special relay (SM) and special register (SD) from being set at the same time by other request sources,
acquiring a right to use of them is required.
A right to use can be acquired when other request sources do not have the right to use them (when SD1361 is '0000H').
1.
Setting a right-to-use request number
Set a request number (a value that has not been used by multiple request sources within the range of '1000H' to '1FFFH') to
SD1360 (iQ Sensor Solution data backup/restoration right-to-use request number).
2.
Requesting a right to use
Turn ON SM1360 (iQ Sensor Solution data backup/restoration right-to-use request) to acquire a right to use for data
restoration. SM1360 turns ON to OFF when the right to use is acquired.
3.
Checking the acquisition of the right to use
Check that the value of SD1361 (iQ Sensor Solution backup/restoration right-to-use acquisition number) is the same as the
value set to SD1360. If backup/restoration is performed without checking the acquisition of the right to use, the normal
operation is not guaranteed.
The values of the special relays (SM) and special registers (SD) for iQ Sensor Solution backup/restoration are
cleared when a right to use is acquired. (However, SD1375 is set to 'FFFFH'.)
Save the values of the special relays (SM) and special registers (SD) as required.
Procedu
re
Item
Reference
1
Acquire a right to use.
Page 300 Acquiring a right to use
2
Set the restoration target setting and the operation setting.
Page 301 Setting the restoration setting
3
Perform a data restoration.
Page 302 Performing a data restoration
4
Release the right to use.
Summary of Contents for 13JV28
Page 1: ...iQ Sensor Solution Reference Manual ...
Page 2: ......
Page 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Page 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Page 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Page 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Page 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Page 373: ...I 371 MEMO ...
Page 377: ......