Setting a target device
• Setting a module
When '1H' (module unit) is set for the execution unit, set a start I/O number to SD1364 (iQ Sensor Solution data backup/
restoration target setting (target module)).
In a multiple CPU system, only the CC-Link IE Field Network master station controlled by a host CPU can be backed up. Data
backup cannot be performed for non-controlled modules.
• Setting a station number
When '2H' (station unit) or '3H' (station sub-ID unit) is set for the execution unit, set a station number to SD1365 (iQ Sensor
Solution data backup/restoration target setting (target device 1)).
• Setting a station sub-ID number
When '3H' (station sub-ID unit) is set for the execution unit, set a station sub-ID number to SD1366 (iQ Sensor Solution
backup/restoration target setting (target device 2)).
When backup/restore the data in a device supporting iQSS which is connected to a bridge module
(NZ2AW1GFAL), set the ID number of AnyWireASLINK to SD1366.
5.
Setting the operation setting when a data backup error occurs
Set the operation to be performed when the data backup fails on some devices while being processed to multiple devices
supporting iQSS to the lower 8 bits of SD1367 (iQ Sensor Solution data backup/restoration operation setting).
Target device (Module)
Description
0 to FFH: Start I/O number
Set the start I/O number (the value obtained by dividing the start I/O number by 16) of the CC-Link IE Field
Network master station which is connected to a target device supporting iQSS.
Target device (Station number)
Description
1 to 120: Station number
Set the station number of a target device supporting iQSS or the station number of the module which is
connected to a device supporting iQSS.
Target device (Station sub-ID
number)
Description
0 to 9999: Station sub-ID number
Set the station sub-ID number of a target device supporting iQSS.
Operation on error
Description
0H: Continue
Set this to continue a data backup even if it fails on some devices.
1H: Stop
Set this to stop a data backup if it fails on some devices.
Summary of Contents for 13JV28
Page 1: ...iQ Sensor Solution Reference Manual ...
Page 2: ......
Page 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Page 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Page 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Page 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Page 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Page 373: ...I 371 MEMO ...
Page 377: ......