40
3 AnyWireASLINK
3.5 Backing up/Restoring Data of Devices Supporting iQSS
4.
Setting a target device
• Setting a module
When '1H' (module unit) is set for the execution unit in the step of 'Setting the execution unit', set the start I/O number of a
target device for data backup to SD1439.
• Setting an ID number
When '2H' (ID unit) is set for the execution unit in the step of 'Setting the execution unit', set the ID number of a target device
for data backup to SD1440.
*1 Specify the a 512 (200H) for an input/combined slave module.
5.
Setting the operation setting when a data backup error occurs
Set the operation on error to the lower 8 bits of SD1444 in order to backup data for multiple devices supporting iQSS.
■
Performing a data backup
Data is backed up if SM1436 is turned ON while SD1446 is '1H' (ready).
Once data is backed up, SD1446 will be '2H' (being executed).
■
Requiring a data backup cancellation
The data backup stops if SM1442 is turned ON while SD1446 is '1H' (ready) or '2H' (being executed).
■
Releasing the right to use
When SM1435 is turned ON after a data backup is completed (including a cancellation or an error), the right to use is released
and the next data backup is ready to be performed.
SM1435 turns ON to OFF when the right to use is released.
If the right to use is released even though it has already been done, SM1435 remains ON since no processing is performed.
In that case, set SM1435 to OFF.
Target device (Module)
Description
0 to FFH: Start I/O number
When '1H' (module unit) is set for the execution unit, set the value obtained by dividing the start I/O number of an
AnyWireASLINK master module, which is connected to a target device supporting iQSS, by 16.
Target device (ID number)
Description
0 to 255 (0FFH): Output slave
module ID number
When '2H' (ID unit) is set for the execution unit, set the ID number of a target device supporting iQSS.
512 (200H) to 767 (2FFH): Input/
combined slave module ID number
Operation on error
Description
0H: Continue
Set this to continue a data backup even if it fails on some devices while being performed to multiple devices supporting
iQSS.
1H: Stop
Set this to stop a data backup even if it fails on some devices while being performed to multiple devices supporting
iQSS.
Summary of Contents for 13JV28
Page 1: ...iQ Sensor Solution Reference Manual ...
Page 2: ......
Page 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Page 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Page 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Page 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Page 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Page 373: ...I 371 MEMO ...
Page 377: ......