244
9 CC-Link IE Field Network
9
CC-Link IE Field Network
This chapter explains the operation methods when using iQ Sensor Solution functions for MELSEC iQ-R series via CC-Link IE
Field Network.
System configuration
This section explains the iQ Sensor Solution functions for CC-Link IE Field Network using the following system configuration.
For details on the devices supporting iQSS and the iQ Sensor Solution functions available for CC-Link IE Field Network, refer
to the following section.
Page 325 Devices that Support iQ Sensor Solution
For information on the engineering tools available for iQ Sensor Solution and the versions of engineering tools supporting
each iQ Sensor Solution function, refer to the following section.
Page 337 Engineering Tool and Version List
• Before using each iQ Sensor Solution function, complete the installation and wiring of the actual system
configuration, and set network parameters and other settings required for communication.
For details on the settings, refer to the following manual.
MELSEC iQ-R Module Configuration Manual
MELSEC iQ-R Ethernet/CC-Link IE User's Manual (Startup)
Considerations when detecting devices supporting iQSS
The following shows the considerations when performing an automatic detection of connected devices for MELSEC iQ-R
series CC-Link IE Field Network.
■
The actual system configuration is not connected/configured properly
An automatic detection of connected devices cannot be performed when the actual system configuration is not connected/
configured properly (duplication of stations, etc.).
In that case, correct the actual system configuration and perform an automatic detection of connected devices again.
■
Information of slave stations is not detected correctly
Information may not be read correctly when performing an automatic detection of connected devices right after a slave station
is connected.
In that case, perform an automatic detection of connected devices again.
■
An extension base unit is connected to the main base unit
When an extension base unit is connected to the main base unit, information of the modules on the extension base unit is
detected as well.
The points of RWr/RWw/RX/RY set to a module on the extension base unit is added to that of the main base unit, and
detected.
Type
Model name
Manufacturer
(1)
Engineering tool
GX Works3
SWnDND-GXW3 ('n' indicates its version.)
Mitsubishi Electric
Corporation
(2)
CPU module
RCPU
R08CPU
(3)
CC-Link IE Field Network-equipped master/local module
RJ71GF11-T2
(4)
Basic Digital Output Module
Screw terminal block type
NZ2GF2B1-16T
NZ2GF2B1-16TE
(1)
(2) (3)
(4)
Summary of Contents for 13JV28
Page 1: ...iQ Sensor Solution Reference Manual ...
Page 2: ......
Page 166: ...164 6 Ethernet 6 5 Backing up Restoring Data of Devices Supporting iQSS MEMO ...
Page 185: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 183 7 Sample program ...
Page 195: ...7 AnyWireASLINK 7 4 Backing up Restoring Data of Devices Supporting iQSS 193 7 Sample program ...
Page 228: ...226 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 238: ...236 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 244: ...242 8 CC Link 8 4 Backing up Restoring Data of Devices Supporting iQSS Sample program ...
Page 309: ...10 Ethernet 10 5 Backing up Restoring Data of Devices Supporting iQSS 307 10 Sample program ...
Page 371: ...APPX Appendix 8 Backup File Capacity 369 A MEMO ...
Page 373: ...I 371 MEMO ...
Page 377: ......