Bytes 0
63
Name
Type of data
Function
Byte 1
Bit 0: MSB
Bit 0: start filling
Bit 1: stop filling
Bit 2: restart filling
Bit 3: cancel filling
Bit 4: load material and start fil-
ling
Bit 5: print last filling result
Bit 6: reserved
Bit 7: reserved
BOOL
Bit 0:
EasyFill adopts the sent material parame-
ters from byte 4 with the rising edge of this
bit. A valid set point (byte 4
7) that can be
coded as DINT or REAL is required.
The filling process can be started when the
ready bit is set.
Bit 1:
rising edge during filling
Bit 2:
rising edge in the stop status (hold state)
Bit 3:
rising edge in the stop status (hold state)
Bit 4:
rising edge: A valid material ID is required
in byte 3.
Bit 5:
rising edge: The printout of the last filling
result starts.
Byte 2
Bit 0: reset power failure (power
fail)
Bit 1: reset error
Bit 2: weights as DINT
Bit 3: zero
Bit 4: tare
Bit 5: reset tare
Bit 6: filling mode
Bit 7: read material from the
material table
BOOL
Bit 0:
rising edge
Bit 1:
rising edge: resets the error flag and error
code.
Bit 2:
status-controlled:
Value: 0 = Real, 1 = DINT
Bit 3:
rising edge
Bit 4:
rising edge
Bit 5:
rising edge
Bit 6:
status-controlled: 0 = fill, 1 = empty
Bit 7:
rising edge: A valid material ID is required
in byte 3. Filling does not start.
This function can be used to display materi-
al parameters on external displays.
Byte 3
Material ID
BYTE
Value range: 1
10
Byte 4
7
Set point
DINT/REAL
Weight
Byte 8
11
Preset
DINT/REAL
Preset point for switching from coarse flow
to fine flow.
Byte 12
15
Material overshoot (OVS)
DINT/REAL
Weight
Byte 16
19
Calming time
DINT
[ms]
Transmitter in field housing PR 5230
12 Fieldbus interface
Minebea Intec
EN-272