4.5.4
Connecting 2
8 load cells (650
Ω
) using a 6-wire connecting cable
Connections are made via junction box PR 6130/.. using connection cable PR 6135/.. or
PR 6136/... .
Load cell supply circuit
-
Load resistance of load cell circuit ≥75
Ω
, e.g. 8 load cells of 650
Ω
each
-
Supply voltage is fixed to 12 V DC and protected against short circuit.
For further technical data, see Chapter
.
4.5.5
Connecting load cells of type series PR 6221
See installation manuals of PR 6221 and PR 6021/08, -/68.
4 Device installation
Transmitter in field housing PR 5230
EN-67
Minebea Intec