TEMPERATURE TRANSMITTER

(HART communication, intrinsically safe/flameproof)

MODEL

FRC

SAFE INSTALLATION MANUAL (IECEx / ATEX APPROVAL)

BEFORE USE ....

 SAFETY PRECAUTIONS

This manual describes important points of caution for safe 
use of this product in potentially explosive atmosphere.
Please read this manual carefully before installing and op-
erating the product.

 SPECIAL CONDITIONS FOR SAFE USE

• If the model FRC0 is mounted in an area where category 1 

equipment is required, precautions have to be taken that 
the enclosure can not be charged by static electricity.

• If the model FRC1 is mounted in an area where category 

1 equipment is required, it must be installed such that 
even in the event of rare incidents, ignition sources due to 
impact and friction sparks are excluded.

• When the model FRC0 is installed in environment requir-

ing a higher ingress protection than IP20, it must be ad-
ditionally protected by an enclosure suitable for the envi-
ronment.

 MANUFACTURED DATE CODE IDENTIFICATION

The manufactured year and moth can be identified by the 
serial number described on the specification label.

Serial No. Y M xxxxxx

YEAR

B : 2021

1 : 2041

C : 2022

2 : 2042

:

:

:

:

U : 2022

9 : 2049

MONTH

2021 - 2049 (year)

M : January

N : February

P March

:

:

Y : December

 MODEL NUMBER IDENTIFICATION

 

 

Model No. FRC                 A

1) ENCOSURE
  0  : None (module only)
  1  : Yes (die cast aluminium)
  2  : Yes (stainless steel casting)

2)  SAFETY APPROVAL
  A  : None
  C : IECEx/ATEX flameproof (for FRC1/FRC2)
  E : ATEX intrinsically safe
 
3)  LCD DISPLAY
  0  : None
  1  : LCD

4)  WIRING CONDUIT
  0  : None (for FRC0)
  1  : 1/2 NPT
  2  : M20 x 1.5
  3  : PG 13.5

 WARNING

Explosions could result in death or serious injury:

• The enclosure cover must be fully engaged to meet flame-

proof requirements.

• Do not remove the enclosure cover in explosive atmos-

pheres when the circuit is alive (except IS models).

• Do not connect or disconnect the LCD module in explosive 

atmosphere when the circuit is alive.

• When the LCD is not installed, covers shall instead be fit-

ted at the open connectors. 

• Before you remove the unit or mount it, or before you con-

nect or disconnect the wiring, turn off the power supply 
and the input signal for safety.  Do not disconnect unless 
the area is known to be non-explosive.

• Whenever you need to measure voltage across the termi-

nals or apply a simulated input signal to the terminals, 
make sure that there is no danger of explosion in the at-
mosphere.

• Before connecting a HART communicator in an explosive 

atmosphere, make sure the instruments in the loop are 
installed in accordance with intrinsically safe field wiring 
practices.

• Verify the certification of the product described on the 

specification label on the product.

• Verify that the operating atmosphere of the transmitter is 

consistent with the appropriate hazardous locations certi-
fications.

• Verify that the environmental temperature is within the 

temperature class required for the area.

Failure to follow these installation guidelines could result 
in death or serious injury:

• Make sure only qualified personnel perform the installa-

tion.

Summary of Contents for FRC

Page 1: ...1 Yes die cast aluminium 2 Yes stainless steel casting 2 SAFETY APPROVAL A None C IECEx ATEX flameproof for FRC1 FRC2 E ATEX intrinsically safe 3 LCD DISPLAY 0 None 1 LCD 4 WIRING CONDUIT 0 None for FRC0 1 1 2 NPT 2 M20 x 1 5 3 PG 13 5 WARNING Explosions could result in death or serious injury The enclosure cover must be fully engaged to meet flame proof requirements Do not remove the enclosure co...

Page 2: ...RC0 in an environment with a high relative humidity exceeding 0 to 95 RH or in a condens ing atmosphere install the unit inside an outdoor enclo sure Model FRC1 FRC2 FLAMEPROOF APPROVAL IECEx Certificate of Conformity IECEx CML 18 0140X Ex db IIC T4 T5 T6 Gb IEC 60079 0 IEC 60079 1 ATEX EU Type Examination Certificate CML 18ATEX1277X II 2G Ex db IIC T4 T5 T6 Gb Zone 1 EN 60079 0 EN 60079 1 Threade...

Page 3: ... to 4 Maximum Output Voltage Uo 6 4 V Maximum Output Current Io 30 mA Maximum Output Power Po 48 mW Maximum External Capacitance Co 20 μF Maximum External Inductance Lo 10 mH NOTES 1 2 In any safety barrier the output current of the barrier must be limited by a resistor R such that Io Uo R The safety barrier must be certified by an EU approved certification body to Ex ia IIC For Zone 1 and 2 Ex ib...

Page 4: ...embly External Earthing Terminal Hazardous Location Zone 1 and 2 Non Hazardous Location PS PS 2 1 INSTALLATION DIAGRAM for IECEx ATEX FLAMEPROOF MODEL ELECTRICAL DATA Power Supply and Supply Voltage 12 to 28 V Output Current 4 to 20 mA Burnout Current 24 mA Sensor Circuit 1 to 4 Input Signal 1 0 V max NOTES 1 2 1 Install per local installation codes IECEx or ATEX approved cable entries or stopping...