WPR2 SERIES

Installation & Operation Instructions

Phone: 

1-888-967-5224

Website: 

workaci.com

GENERAL INFORMATION

The ACI WPR2 Series Remote Wet to Wet 

Differential Pressure Transmitter is designed to 

reduce installation time and provide mounting 

flexibility, often eliminating the need for 

additional plumbing and manifolds. The WPR2 

can be ordered with standard CMP rated PVC 

cable or with a metal clad cable. The metal clad 

cable provides end to end protection of the 

cables with flexible metal conduit, durable and 

resistant 304 stainless steel construction. The 

WPR2 accurately measure wet media pressures 

in a variety of applications. Commonly used 

for monitoring pumps, these devices are also 

ideal for measuring pressure across filters, heat 

exchangers and compressors. The dual remote 

sensors are based on a ceramic capacitive 

sensing element with ¼”-18 NPT male (304 

stainless steel) fittings. The WPR2’s enclosure 

opens conveniently to allow it to be reconfigured 

between three additional ranges and outputs of 

4 to 20 mA , 0 to 5 VDC, or 0 to 10 VDC (default). 

The different configurations in this series can 

measure both uni or bi-directional pressure 

ranges as low as 3 psi and as high as 300 psi, 

depending on the unit.

Precautions:

• 

Do not switch pressure range and output 

mode when power is on. Make sure 

to power off the unit first, then move 

jumpers to the correct positions and 

then power on the transmitter.

• 

Do not apply any external voltage to 

zero terminals.

• 

Do not replace pressure sensors with any 

other sensors.  Do not interchange the 

high and low sensors. The high and low 

sensors are specifically calibrated to the 

WPR2 unit. 

Any changes to the sensors will void the 

product warranty

MOUNTING INSTRUCTIONS

The WPR2 is supplied with 4 mounting flanges. 

The mounting flanges must be installed onto 

the bottom of the enclosure. Align the mounting 

flanges with the threaded insert on the bottom 

of the enclosure. Insert and tighten down the 

screws. 

Summary of Contents for WPR2 Series

Page 1: ...d on a ceramic capacitive sensing element with 18 NPT male 304 stainless steel fittings The WPR2 s enclosure opens conveniently to allow it to be reconfigured between three additional ranges and outpu...

Page 2: ...r use the dimensions listed in FIGURE 1 p 1 to measure out Output Signal SW8 Output Mode SW7 Position 2 Supply Voltage Wire Connection Vout 0 5 VDC 5V VAC VDC V COM VOUT Vout 0 10 VDC 10V VAC VDC V CO...

Page 3: ...ared transformer If the 24 VDC or 24VAC power is shared with devices that have coils such as relays solenoids or other inductors each coil must have an MOV DC AC Transorb Transient Voltage Suppressor...

Page 4: ...he corresponding terminal block inside the housing Otherwise ACI will not guarantee the accuracy specifications DO NOT REPLACE SENSORS WITH ANY OTHER SENSORS THEWPR2 UNITS ARE CALIBRATEDWITHTHE HIGH A...

Page 5: ...2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A...

Page 6: ...able for pressures over 100 PSI Verify the HIGH Sensor Voltage is between 0 5 VDC 0 PSI and 4 5 VDC Max Line Pressure When measuring from the HIGH Sensor terminal block GND Black Wire to OUT White Wir...

Page 7: ...60 C Storage Temperature 13 to 176 F 25 to 80 C Operating Humidity 10 to 90 RH non condensing Proof Pressure A WPR2 30 Series and A WPR2 100 Series 3X FS A WPR2 300 Series 2X FS Burst Pressure 1500 p...

Page 8: ...Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Version 22 0 I0000756...