Gate
Original point sensor
CLOSE side
limit sensor
When the gate is in the direction of CLOSE side.
Gate
CLOSE side limit sensor
OPEN side
limit sensor
CAUTION
Warning of personal injury and damage to property.
There is a possibility that the gate is overrun according to the calibration value or the
system composition.
Execute calibration of manual speed, refer to Chapter
.
Note:
Mount the original point sensor on an appropriate position. When the position of the
original point sensor is improper, the original point cannot be correctly detected.
7.6.5
Full open position calibration TYPE1 (FULL OPEN TYPE 1)
The operator moves the gate manually, and conirms that the gate comes to the position
of full open at sight.
That position is calibrated as a full open position.
Gate
Original point
Full open position
The gate moves in the direction of Full open position
The gate moves in the direction of CLOSE side.
3. Tap [START].
After the CLOSE side limit sensor is detected, it moves in the direction of OPEN.
When [STOP] is tapped, the gate stops.
The gate moves in the direction of CLOSE.
4. Tap [OK].
1. Select [FULL OPEN TYPE1] in the screen of position calibration.
2. Select [MANUAL SPEED] in the screen of full open position calibration TYPE1.
3. After selecting the speed in manual operation from [LOW SPEED] or [HIGH SPEED],
tap [OK].
4. After selecting from [OPEN] or [CLOSE] in the screen of full open position calibration
TYPE1, stop the gate at full open position at sight.
Weight Controller CSD-918
7 Servo calibration
EN-66
Minebea Intec