Page 17
Installation and Mounting
CSP2008
4.3.1.1 Power Supply
Connect the inputs
24 V
and
0 V
to a 24 V power supply.
MICRO-EPSILON recommends the use of the optionally available power supply PS2020
for the controller. Features: DIN rail mounting, input 230 VAC, output 24 VDC/2.5 A.
ESC
L1
+
+
N
PS2020
Sync/T
rig
Shield
Shield
Shield
Ana1
Out1
Out2
Sync/Out
GND
GND
GND
GND
GND
A
Shield
Ana2
GND
A
Zero
GND
Laser
GND
24V
PE
PE
0V
230 VAC
Protective earth
conductor
Fig. 9 Power supply of the CSP2008 with a PS2020
4.3.1.2 Laser Switch On
The digital input has overload and reverse polarity protection.
Connect the inputs
Laser
and
GND
in order to switch on the laser beam of the con-
nected sensors, see
Fig. 7
, see
Fig. 10
.
A connection of the input to
GND
using a button or a transistor (NPN - Open Collector) is
sufficient for starting.
The laser beam of the connected sensors is switched off for open inputs.
VCC
3.3 V
GND
2.2pF
20 kOhm
4.8 kOhm
GND
GND
Zero/Laser/Sync_Trig
CSP2008
Sync/T
rig
Shield
Shield
Shield
Ana1
Out1
Out2
Sync/Out
GND
GND
GND
GND
GND
A
Shield
Ana2
GND
A
Zero
GND
24V
24V
PE
PE
0V
0V
Fig. 10 Input circuit (TTL) for reset (Zero), laser and synchronization / triggering
(Sync_Trig)
4.3.1.3 Inputs for Reset, Synchronization and Triggering
The digital inputs have overload and reverse polarity protection.
Connect the inputs
Zero
or
Sync/Trig
to
GND
in order to initiate the function, see
Fig. 7
, see
Fig. 10
.
A connection of the input to
GND
using a button or a transistor (NPN - Open Collector) is
sufficient for starting.
The direction (LOW or HIGH) of the activated input
Sync/Trig
or reset (
Zero)
is speci-
fied in the basic settings of the terminal block, see Chap.
5.3.6.1
.