Appendix - "Bus analysis" mode
134
12.12.3. Measurements (Profibus DP)
Diagnosis
Use this table to troubleshoot problems on a measurement :
Measurement
Description
Diagnosis
VOffset
Offset measurement on the
RxD-P or TxD-P signal
Chassis-ground disturbance problem
Common mode problem
Cable length not compliant with standard
….
VLevel
Signal amplitude measurement ((RxD-
P/TxD-P) -(RxD-N/TxDN))
Termination problem
Junction connection (oxidation, bad contact,
etc.)
Cable length not compliant with standard
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
Time Data
Measurement made using the bit time
total.
Unsuitable or damaged cable
Termination impedance incorrectly positioned
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
Time Rise
Rise time between 10% and 90% of
the signal amplitude
Unsuitable or damaged cable (the rise and fall
times increase with the cable impedance)
Termination impedance incorrectly positioned
…
Time Fall
Fall time between 90% and 10% of
the signal amplitude
Jitter
Measurement made using the bit time
total
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
Over+
Measurement of the positive
overshoot compared to the signal
amplitude
Unsuitable cable impedance
Termination problem (if there is no termination,
major overshoot and the opposite if the bus
impedance is too high)
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
Over-
Measurement of the negative
overshoot compared to the signal
amplitude