Appendix - "Bus analysis" mode
114
12.2.3. Measurements (AS-I)
Diagnosis
Use this table to troubleshoot problems on a measurement :
Measurement
Description
Diagnosis
VAmp
Measurement of the amplitude of the
signal's AC component
Termination problem (load too light)
Cable length not compliant with standard
Faulty junction connection (oxidation, bad
contact, etc.)
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
Time Data
Measurement made using the bit time
total.
The bit time is measured over one
period, because the
AS-I bus uses Manchester coding.
VBat
Measurement of the offset of the DC
part of the signal.
This corresponds to the AS-I bus
power supply.
Unsuitable or damaged cable (load too light)
Cable length not compliant with standard
Faulty junction connection (oxidation, bad
contact, etc.)
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…