Appendix - "Bus analysis" mode
128
12.9.3. Measurements (KNX)
Diagnosis
Use this table to troubleshoot problems on a measurement :
Measurement
Description
Diagnosis
VPower
Measurement of the KNX signal offset
(power supply)
Too many devices on the bus
Cable length not compliant with standard
Faulty power supply
…
VLow Active
Negative pulse low-level
measurement
Faulty transmitter
Cable length not compliant with standard
Termination problem
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
Faulty junction connection (oxidation, bad
contact, etc.)
…
VMax equalisation
Measurement of the signal high level
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
Faulty transmitter
…
Uend equalisation
Voltage level compared to VPower
after 104µs.
The 104µs are measured from the
falling edge of the low pulse.
Faulty transmitter
Cable length not compliant with standard
Termination problem
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
Faulty junction connection (oxidation, bad
contact, etc.)
…
TActive
Measurement made using the bit time
total. Bit time measured only on low
pulses.
Faulty transmitter
Cable length not compliant with standard
Termination problem
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
Faulty junction connection (oxidation, bad
contact, etc.)
…